Item 

Specification 

Protection 

Input overvoltage 
protection   

Protection point: > 300 V AC 

Recovery range: 290-300 V AC 

Input undervoltage 
protection 

Protection point: < 80 V AC 

Recovery range: 70-85 V AC 

Output overvoltage 
protection 

56

–60V DC 

(can be set by monitoring unit) 
1. If the overvoltage occurs inside the 

rectifier due to a fault, the rectifier 
will latch off.  

2. If  the output voltage is higher than 

63 V and lasts for more than 500 
ms, the rectifier will latch off. 

Output current 
limiting protection 

See Figure 1. 

Output short circuit 
protection 

A long term short circuit is allowed. 
After the fault is rectified, the rectifier 
is restored to a healthy state 
automatically. 

Over-temperature 
protection 

The module protects against 
overtemperature. 

Safety/EMC/Lightening protection 

Safety 
certification 

Passes TUV, CE, UL certifications. 
Catch the CB certificate. 
Complies with  
UL60950-1; 
IEC60950-1; 
EN60950-1; 
CAN/CSA C22.2 No. 60950-1; 

EMC 

EN55022 Class B ; 
EN55024; 
EN61000-3-2; 
EN61000-3-3; 
ETSI EN300 386; 
ETSI EN301489; 
ITU-T K.20; 

Lightning 

5 kA 

Reliability 

MTBF 

> 500,000 hours 

Audible Noise 

Specification 

≤ 40 dB (25ºC

/77°F

, full load) 

Output Feature 

Figure 1 Output feature 

 

 

 

 

 

 

 

 

 

 

 

Figure 2 Efficiency 
(Vin = 230 V AC, Vout = 53.5 V, Ta: 25ºC) 

 

 

 

 

 

 

 

 

 

 

 

Figure 3 Power derating curve

 

 

Other Features 

0

200

400

600

800

1000

1200

-40

-20

0

20

40

60

80

P

o

(w

)

Ta(

)

Power Derating Curve 

Summary of Contents for R4815N1

Page 1: ... V AC 30 100 load Height x Width x Depth 40 8 mm x 95 5 mm x 208 mm 1 61 in x 3 76 in x 8 19 in Weight About 1 1 kg Cooling Built in fan The rotation of fan depends on the internal temperature Description The R4815N1 is a digital rectifier with high efficiency and power density It converts 85 300 V AC input voltage to 53 5 V DC output voltage The output voltage can be adjusted by the host It perfo...

Page 2: ...ong term short circuit is allowed After the fault is rectified the rectifier is restored to a healthy state automatically Over temperature protection The module protects against overtemperature Safety EMC Lightening protection Safety certification Passes TUV CE UL certifications Catch the CB certificate Complies with UL60950 1 IEC60950 1 EN60950 1 CAN CSA C22 2 No 60950 1 EMC EN55022 Class B EN550...

Page 3: ... the guide rail and push the locking latch right to fix the handle as shown in Figure 6 Transport The product must be packed with firmly packing box when transport Out of the box the mark prevent moisture lay down carefully and other required mark must have Any transport tools are permitted if the product in the packing box When transport must avoid rain and snow attack directly and mechanical sho...

Page 4: ...voltage protection Check that the electrical grid voltage is within a normal range The rectifier is hibernated No measure is required Blinking at 0 5 Hz The rectifier communication is interrupted Replace the rectifier or monitoring module Fault indicator Red Off The rectifier is not faulty No measure is required Steady on The rectifier is locked due to output overvoltage Pull out the rectifier and...

Reviews: