2
R4815N1 Rectifier User Manual V1.2
Item
Specification
Protection
Input overvoltage
protection
Protection point: > 300 V AC
Recovery range: 290-300 V AC
Input undervoltage
protection
Protection point: < 80 V AC
Recovery range: 70-85 V AC
Output overvoltage
protection
56
–60V DC
(can be set by monitoring unit)
1. If the overvoltage occurs inside the
rectifier due to a fault, the rectifier
will latch off.
2. If the output voltage is higher than
63 V and lasts for more than 500
ms, the rectifier will latch off.
Output current
limiting protection
See Figure 1.
Output short circuit
protection
A long term short circuit is allowed.
After the fault is rectified, the rectifier
is restored to a healthy state
automatically.
Over-temperature
protection
The module protects against
overtemperature.
Safety/EMC/Lightening protection
Safety
certification
Passes TUV, CE, UL certifications.
Catch the CB certificate.
Complies with
UL60950-1;
IEC60950-1;
EN60950-1;
CAN/CSA C22.2 No. 60950-1;
EMC
EN55022 Class B ;
EN55024;
EN61000-3-2;
EN61000-3-3;
ETSI EN300 386;
ETSI EN301489;
ITU-T K.20;
Lightning
5 kA
Reliability
MTBF
> 500,000 hours
Audible Noise
Specification
≤ 40 dB (25ºC
/77°F
, full load)
Output Feature
Figure 1 Output feature
Figure 2 Efficiency
(Vin = 230 V AC, Vout = 53.5 V, Ta: 25ºC)
Figure 3 Power derating curve
Other Features
0
200
400
600
800
1000
1200
-40
-20
0
20
40
60
80
P
o
(w
)
Ta(
℃
)
Power Derating Curve