Huawei R4815N1 User Manual Download Page 3

R4815N1 Rectifier User Manual V1.2 

Interface Description 

The rear panel of the rectifier provides an golden finger 
connection which is used as AC input, DC output and 
signal connection.For the location of the pins, see 
Figure 3. For the definitions of the pins, see Table 1. 

Figure 4 Pins on the rear panel 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 1 Definitions of the pins on the rear panel 

Pin 

Definition 

Function 

1, 9 

Live line 

2, 10 

Neutral line 

3, 11 

PE 

Protect earth 

CANL 

CANL 

13 

ACD1 

Slot detection signal 1 

 5 

ACD2 

Slot detection signal 2 

12 

CANH 

CANH 

6, 14 

 

Output:48V+ 

OUTPUT- 

Output:48V- 

 7 

Pre-charge 

Pre-charge 

Removing the Rectifier 

Figure 5   Removing a PSU 

 

 

 

Step 1: Push the locking latch left. 

Step 2: Remove the PSU out of the PDU by 

externally drawing the handle, as shown 
in Figure 5. 

Installing the Rectifier 

Figure 6   Installing a PSU 

 

 

 

Step 1: Push the locking latch left and pull out  the 

handle. 

Step 2: Push the PSU slowly into the subrack 

along the guide rail and push the locking 
latch right to fix the handle, as shown in 
Figure 6. 

Transport 

The product must be packed with firmly packing 
box when transport. Out of the box the mark 
“prevent moisture”, “lay down carefully” and other 
required mark must have. Any transport tools are 
permitted if the product in the packing box. When 
transport must avoid rain and snow attack directly 
and mechanical shock. 

Storage 

Product should be packaged in the packing box 
before use. The store room should be meet:  
-40ºC to +70ºC ambient temperature, related 
humidity less than 80%, dry, ventilation and hasn’t 
any corrosive gas. 

 

 
 

 

Only trained and qualified personnel can be allowed to 
install or service the rectifier. 

Each rectifier input is protected by two fuses, one for the 
live wire and the other for the neutral wire. 

CAUTION

This product should be used in the environment that meets 
specifications described in the user manual. 

If the product is used with abnormal power grid input or 
exposed to salt mist, dust, or mist, the product may become 
faulty, and the resulting product exceptions or component 
damage are beyond the warranty scope. 

CAUTION

Summary of Contents for R4815N1

Page 1: ... V AC 30 100 load Height x Width x Depth 40 8 mm x 95 5 mm x 208 mm 1 61 in x 3 76 in x 8 19 in Weight About 1 1 kg Cooling Built in fan The rotation of fan depends on the internal temperature Description The R4815N1 is a digital rectifier with high efficiency and power density It converts 85 300 V AC input voltage to 53 5 V DC output voltage The output voltage can be adjusted by the host It perfo...

Page 2: ...ong term short circuit is allowed After the fault is rectified the rectifier is restored to a healthy state automatically Over temperature protection The module protects against overtemperature Safety EMC Lightening protection Safety certification Passes TUV CE UL certifications Catch the CB certificate Complies with UL60950 1 IEC60950 1 EN60950 1 CAN CSA C22 2 No 60950 1 EMC EN55022 Class B EN550...

Page 3: ... the guide rail and push the locking latch right to fix the handle as shown in Figure 6 Transport The product must be packed with firmly packing box when transport Out of the box the mark prevent moisture lay down carefully and other required mark must have Any transport tools are permitted if the product in the packing box When transport must avoid rain and snow attack directly and mechanical sho...

Page 4: ...voltage protection Check that the electrical grid voltage is within a normal range The rectifier is hibernated No measure is required Blinking at 0 5 Hz The rectifier communication is interrupted Replace the rectifier or monitoring module Fault indicator Red Off The rectifier is not faulty No measure is required Steady on The rectifier is locked due to output overvoltage Pull out the rectifier and...

Reviews: