Huawei R4815N1 User Manual Download Page 1

R4815N1 Rectifier User Manual V1.2 

Environmental Specifications 

Item 

Specification 

Operating 
temperature     

–40ºC to +75 ºC (referring to Figure 3) 
(

–40

°

F to +167

°

F)  

Storage 
temperature 

–40ºC to +75ºC (not packaged) 
(

–40

°

F to +167

°

F)  

Relative humidity  5%-95% (non-condensing) 

Altitude range 

≤ 4000 m 

Item 

Specification 

Input 

Operating voltage 
       

85

–300 V AC 

Rated: 200

–240 V AC and  

100

–120 V AC 

Frequency 

45

–66 Hz 

Rated: 50 Hz and 60 Hz 

Maximum input 
current 

≤ 6.4 A 

Power factor 

 0.99 (100% load)   

THD 

≤ 3.5% (full load) ;  
≤ 5% (load 

≥ 50

%) 

Output 

Output voltage 
       

42

–58 V DC 

Rated voltage: 53.5 V DC 

Output power 

1000 W (176

–300 V AC); 

470 W (85

–175 V AC decreased linearly)  

Regulated voltage 
precision 

≤ 

±

0.6%Vo 

Ripple and noise 

≤ 200 mVp-p 
(Bandwidth 

≤ 20M Hz) 

Dynamic response 

25-50% or 50-75% load 

−Over shoot:≤ 

±

5%  

−Recovery time: ≤ 200 us (

±

0.6%) 

10-90% load; 

−Over shoot:≤ 

±

5%; 

−Recovery time: ≤ 1ms (

±

1%) 

Standby power 

≤ 5 W 

Turn-on output 
delay 

3

–8s 

Hold up time 

> 10 ms 

Psophometrically 
weighted noise 

≤ 2 mV 

Broad frequency 
noise voltage 

≤ 50 mV (3.4–150 kHz) 
≤ 20 mV (0.15–30 MHz) 

Electrical Specifications 

Efficiency 

The peak point is 

≥ 

94% 

≥ 

93% (230 V AC, 30%

–100% load)  

Height x Width x 
Depth 

40.8 mm x 95.5 mm x 208 mm 
(1.61 in. x 3.76 in. x 8.19 in.) 

Weight 

About 1.1 kg 

Cooling 

Built-in fan (The rotation of fan depends 
on the internal temperature.) 

Description 

The R4815N1 is a digital rectifier with high efficiency and 
power density. It converts 85

–300 V AC input voltage to 

53.5 V DC output voltage. The output voltage can be 
adjusted by the host. 

It performs comprehensive protection functions, supports 
soft start, and produces low noise. With the latest power 
monitoring technology, states of the rectifier and load are 
monitored in real time.  

Multiple rectifiers can be paralleled.  

Key Features 

Input voltage range: 85

–300 V AC 

Operating temperature range: 

–40ºC to +75ºC 

Total harmonic distortion (THD): ≤ 3.5

 

Digital control mode 

Hot swap 

Supports intelligent electric meter 

Supports CAN communication 

Supports LED display 

Supports voltage adjustment,current 
adjustment,and current sharing 

Meet Rohs requirement 

Passes the TUV, CE, UL certifications and gets 
the CB certifIcate. 

Disconnect above 320 V AC 

 

 
 
 

Note

: If the altitude is within the range of 3000 m to 4000 m, the maximum operating 

temperature decreases by 1

°

C (1.8

°

F ) as the altitude increases by 200 m. 

Copyright © Huawei Technologies Co., Ltd. 2016. All rights reserved. 

Summary of Contents for R4815N1

Page 1: ... V AC 30 100 load Height x Width x Depth 40 8 mm x 95 5 mm x 208 mm 1 61 in x 3 76 in x 8 19 in Weight About 1 1 kg Cooling Built in fan The rotation of fan depends on the internal temperature Description The R4815N1 is a digital rectifier with high efficiency and power density It converts 85 300 V AC input voltage to 53 5 V DC output voltage The output voltage can be adjusted by the host It perfo...

Page 2: ...ong term short circuit is allowed After the fault is rectified the rectifier is restored to a healthy state automatically Over temperature protection The module protects against overtemperature Safety EMC Lightening protection Safety certification Passes TUV CE UL certifications Catch the CB certificate Complies with UL60950 1 IEC60950 1 EN60950 1 CAN CSA C22 2 No 60950 1 EMC EN55022 Class B EN550...

Page 3: ... the guide rail and push the locking latch right to fix the handle as shown in Figure 6 Transport The product must be packed with firmly packing box when transport Out of the box the mark prevent moisture lay down carefully and other required mark must have Any transport tools are permitted if the product in the packing box When transport must avoid rain and snow attack directly and mechanical sho...

Page 4: ...voltage protection Check that the electrical grid voltage is within a normal range The rectifier is hibernated No measure is required Blinking at 0 5 Hz The rectifier communication is interrupted Replace the rectifier or monitoring module Fault indicator Red Off The rectifier is not faulty No measure is required Steady on The rectifier is locked due to output overvoltage Pull out the rectifier and...

Reviews: