9 Power-on and Commissioning
Issue 03 (2020-04-10)
Copyright © Huawei Technologies Co., Ltd.
77
Table 9-8
Changing the language
Path
Parameter
Setting
System Info
>
Settings
>
Basic
Set Local LUI Language
Select a desired language.
After the MDU language is changed, the LUI language will automatically switch to the language set on
the LUI at the same time.
Step 4
Set the parallel ID.
In the case of multiple parallel scenarios in the same LAN, you need to set the two parallel cabinets to a
unified parallel identifier to distinguish the parallel status of the cabinets.
Table 9-9
Setting the parallel ID
Path
Parameter
Default Value
Setting
System Info
>
Settings
>
Basic
Param.
Parallel ID
-
'a~z', 'A~Z', '0~9', '_'
(Max. 15
Characters)
Step 5
Set the monitor parallel IP address.
In the parallel scenario, you need to set the monitor parallel IP address. The IP addresses of the master
and slave devices must be in the same network segment.
Table 9-10
Setting the monitor parallel IP address
Path
Parameter
Default Value
Setting
System Info
>
Settings
>
Communication
Monitor Parallel IP
Address
192.168.023.200
Set this parameter
based on the address
assigned by the
network
administrator.
Step 6
Set NetEco configuration parameters.
In a parallel system, this parameter needs to be set only for the master unit.