5 Troubleshooting
Issue 03 (2019-05-20)
Copyright © Huawei Technologies Co., Ltd.
40
5
Troubleshooting
describes common faults and troubleshooting measures.
Table 5-1
Common faults and troubleshooting measures
Symptom
Possible Causes
Solution
The circuit breaker is ON
but no power is supplied
to the UPS.
The circuit breaker is
faulty.
Replace the BCB box.
The battery cable is loose
or disconnected.
Connect the cable securely.
The circuit breaker
cannot be switched to the
OFF position.
The circuit breaker is
faulty.
Replace the BCB box.
The BCB is OFF, but the
UPS LCD displays an
alarm indicating that the
BCB is ON.
The DIP switch settings are
incorrect.
Check the DIP switch settings.
The circuit breaker
cannot trip properly.
The control board fails.
Replace the BCB box.
The circuit breaker fails.
For any difficulty, contact Huawei technical support.