PDU8000-(0125, 0250, 0400, 0630, 0800)
DCV8-BXA001 Battery Circuit Breaker Box
User Manual
3 Installation
Issue 03 (2019-05-20)
Copyright © Huawei Technologies Co., Ltd.
16
Terminal Number of
Terminals and
Hole Diameter
Recommended
Cable
Specifications
Recommende
d Wiring
Terminal
Recommended
Bolt
Specifications
Recommended
Cable Color
4 x M10
(through-hole)
PE
1 x M10 (rivet
nut)
1 x 70 mm
2
70-M10
M10 x 25
Green-and-yello
w
PDU8000-0630DCV8-BXA001 Cables
Table 3-4
Specifications for PDU8000-0630DCV8-BXA001 cables and terminals
Terminal
Number of
Terminals and
Hole Diameter
Recommended
Cable
Specifications
Recommende
d Wiring
Terminal
Recommende
d Bolt
Specifications
Recommended
Cable Color
UPS+
2 x M12
(through-hole)
1 x (2 x 150 mm
2
) 150-M12
2 x (M12 x 45)
Red
UPS N
2 x M12
(through-hole)
1 x (2 x 150 mm
2
) 150-M12
2 x (M12 x 45)
Blue
UPS–
2 x M12
(through-hole)
1 x (2 x 150 mm
2
) 150-M12
2 x (M12 x 45)
Black
BAT+
2 x M12
(through-hole)
1 x (2 x 150 mm
2
) 150-M12
2 x (M12 x 45)
Red
BAT N
2 x M12
(through-hole)
1 x (2 x 150 mm
2
) 150-M12
2 x (M12 x 45)
Blue
BAT–
2 x M12
(through-hole)
1 x (2 x 150 mm
2
) 150-M12
2 x (M12 x 45)
Black
PE
1 x M12
(through-hole)
1 x 150 mm
2
150-M12
M12 x 45
Green-and-yello
w
PDU8000-0800DCV8-BXA001 Cables
Table 3-5
Specifications for PDU8000-0800DCV8-BXA001 cables and terminals
Terminal Number of
Terminals and
Hole Diameter
Recommended
Cable
Specifications
Recommended
Wiring
Terminal
Recommende
d Bolt
Specifications
Recommended
Cable Color
UPS+
2 x M16
(through-hole)
1 x (2 x 185 mm
2
) 185-M16
2 x (M16 x 60)
Red
UPS N
2 x M16
(through-hole)
1 x (2 x 185 mm
2
) 185-M16
2 x (M16 x 60)