Compon
ent
Item
Troubleshooting
Humidit
y and
tempera
ture
sensor
Humidity and temperature
sensors in smart cooling
products and aisles are
securely installed.
Secure the sensors again by
referring to
Humidity and Temperature Sensor
Water
sensor
The water sensor is secure,
and the two downward metal
conductive plates do not
interfere with each other or
corrode.
Replace the water sensor by
referring to
Compressor Oil Level
You can view the refrigerant oil status from the oil sight glass of the compressor.
shows the normal and abnormal refrigerant oil states.
Water Sensor
When the pair of terminals of the water sensor detect water or other conductive
liquid, resistance between the two terminals decreases. During the maintenance,
check that the two detection terminals, as shown in
, are free from
corrosion, foreign matter, and connection in between.
Figure 6-2 Water sensor detection terminals
(1) Detection terminals
6.2.5 Quarterly Maintenance