4 Alarms and Faults
Issue 01 (2016-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
53
A fire can seriously affect the stable running of the system and equipment safety. Therefore,
any fire alarm must be immediately handled.
4.8 Fire Alarms (CE)
Fault
Category
Alarm
Severity
Symptom
Possible
Cause
Troubleshooting
LOCAL
FIRE
Critical
For details about how to handle a gas release fire alarm, see
Emergency Operations for a Gas Release Alarm (CE)
FAULT
RELAY
Major
See the documents delivered with the fire control panel.
A fire can seriously affect the stable running of the system and equipment safety. Therefore,
any fire alarm must be immediately handled.
4.9 Temperature Alarms
Fault
Category
Alarm
Severity
Symptom
Possible
Cause
Troubleshooting
Overtemp
erature
Critical
The onsite
temperature is too
high.
The air
conditioners are
powered off.
Check whether the
circuit breaker is
OFF in the PDC.
Check whether the
air conditioner
power cables are
connected properly.
The air
conditioners are
not turned on.
Turn on the air
conditioners.
The air
conditioner is
not properly
set.
Verify that the initial
configurations of the
air-cooled precision air
conditioner are
consistent with the
initial configuration
requirements initial
configuration guide.