FusionModule1000A20 CT Solution
Maintenance Guide
5 Parts Replacement
Issue 01 (2019-02-25)
Copyright © Huawei Technologies Co., Ltd.
80
Procedure
Step 1
Remove cables connected to the AI/DI module.
When removing cables, label the cables with corresponding terminal ports for later
connection.
After removing cables, wrap exposed terminals with insulation tape.
Step 2
Remove the faulty AI/DI module from the cabinet.
Step 3
Install a new AI/DI module on the rack.
Figure 5-11
Installing an AI/DI module
Step 4
Connect cables to the new AI/DI module.
Step 5
Configure the AI/DI module based on the management system initial configuration table.
----End
Follow-up Procedure
Dispose of the removed AI/DI module that is confirmed faulty.
5.3.4 Replacing a Smart ETH Gateway
Prerequisites
A spare ETH gateway of the same model is available and functional.
Impact on the System
Devices connected to the ETH gateway will be disconnected.