FusionModule1000A20 CT Solution
Maintenance Guide
3 Routine Maintenance
Issue 01 (2019-02-25)
Copyright © Huawei Technologies Co., Ltd.
17
Categ
ory
Mainten
ance
Item
Operation
Check
Standard
Troubleshooting
ution
System
Check whether
the indicators are
normal.
All indicators
are normal.
Rectify the fault by
referring to
TP48200B-N20B2 &
TP48200B-N20B3 &
TP48200B-L20B2 &
TP48400B-N20B3 &
TP48400B-L20B1
V500R002 User Manual
.
Check whether
the ground points
properly connect
to the equipment
room ground bar.
The cable
between the
power system
ground point
and the
equipment room
ground bar is
securely
connected.
Secure the ground point or
replace the ground cable.
PDC
Check the
luminance of the
indicators.
The three-phase
power indicators
are steady on.
If an indicator is off or dim,
replace it. For details, refer
to 5.1.2.5 Replacing an
Indicator.
Check the SPD
indicator and
SPD circuit
breaker status.
The SPD
indicator is
green.
If the SPD indicator is red,
replace the SPD. For
details, refer to 5.1.2.4
Replacing an SPD.
The SPD circuit
breaker is
switched to ON.
1.
If the SPD indicator is
red, replace the SPD.
For details, refer to
5.1.2.4 Replacing an
SPD.
2.
Switch on the circuit
breaker.
ECC80
0
WebUI
FusionMo
dule1000
alarms
On the ECC800
WebUI, choose
Home
>
Active
Alarms
or
Query
>
Historical
Alarms
.
No alarm is
displayed in the
alarm
information
area.
Refer to
ECC800 Data
Center Controller
V100R001C30 User
Manual
or iManager
NetEco documentation.
Alarm short
messages can be
received.
Check whether the SIM
card is properly installed. If
the SIM card is faulty,
replace it by following
instructions in
ECC800
Data Center Controller
V100R001C30 User
Manual
.