22
The table uses 8 devices in CAN teamwork as an example.
Item
Parameter
Principle
No.
1
2
...
7
8
Smart cooling product No.
Teamwork
group No.
1
1
...
1
1
A teamwork network can contain
a maximum of four groups, which
can be numbered 1 to 4
respectively. Smart cooling
products in a group must have the
same teamwork group number.
System address
1
2
...
7
8
In a teamwork group, the smart
cooling product address (1–32)
must be unique and the unit with
the smallest address is the master
unit.
Enable
teamwork CAN
resistor
Yes
No
...
No
Yes
This parameter is mandatory in
CAN networking. The first and last
devices should be set to
Yes
.
Teamwork
function
Enable
Enable
...
Enable
Enable
/
Networking
mode
CAN
network
CAN
network
...
CAN
network
CAN
network The networking mode set on the
screen must be consistent with the
actual networking mode.
FE
network
FE
network
...
FE
network
FE
network
Number of
systems in this
group
8
/
...
/
/
The value ranges from 1 to 32.
Number of
running
systems in this
group
6
/
...
/
/
The value ranges from 1 to the
number of units in the group.
Except the running units in the
group, other units in the group are
used as standby units.
Rotation
function
Enable
/
...
/
/
When the rotation function is
enabled, the active and standby
units can work alternately. It is
recommended that this function
be enabled when the load field is
even.
5.
(Optional) Set teamwork parameters. On the home screen, choose >
Teamwork
Settings
. The
Teamwork Settings
screen is displayed.