21
9
Power-On Commissioning
Power-On
9.1
1. Turn on the switch in the upstream PDF.
2. Turn on all switches of the device.
3. If the device is powered on for the first time, the
Quick Settings
screen is displayed. Set the
language, date format, date, time, time zone, teamwork control, system, optional components,
T/H sensors, and communications parameters. If the device is not powered on for the first
time, the home screen is displayed automatically.
4. (Optional) Set monitoring parameters.
Users are classified into two types:
operator
(preset password:
000001
) and
admin
(preset
password:
000001
).
After power-on, the device is in the shutdown state.
After power-on, the compressor starts preheating, and the system generates a compressor
preheating alarm. The preheating takes 12 hours. Before the compressor is preheated, the
device cannot be powered on. To obtain the remaining preheating time of the compressor,
choose
Running
>
Device Details
>
Compressor
.
Northbound RS485 Monitoring (Modbus_RTU Protocol)
a. On the home screen, choose
Settings
>
Comm Settings
>
Modbus Settings
and set the
baud rate to be the same as that on the network management system (NMS).
b. Set the communications address. The communications addresses of the two smart cooling
products connected to the same NMS must be different.
FE Monitoring (Modbus_TCP Protocol)
c. Set
RS485 monitoring grouping
.
For scenarios without grouping, set this parameter to
Enable
for the last device.
For scenarios with grouping, set this parameter to
Enable
for the last device in each
teamwork control group.
a. (LAN settings) On the home screen, choose
Settings
>
Comm Settings
>
LAN IP Settings
and set
LAN IP address assignment mode
to
Manual
. Set
LAN IP address
,
LAN subnet
mask
, and
LAN gateway
according to the actual planning.
b. (WAN settings) On the home screen, choose
Settings
>
Comm Settings
>
WAN IP Settings
.
Set
IP address
,
Subnet mask
, and
Gateway
according to the actual planning.
c. On the home screen, choose
Settings
>
Comm Settings
>
Modbus Settings
. Set
Link mode
to
Server and client
or
Client
, and set
Client encryption
to
Enable
.
d. Enter the actual IP address of the NMS.
e. When
Client encryption
is set to
Enable
, set
NMS port number
to
32907
. When
Client
encryption
is set to
Disable
, set
NMS port number
to
32906
.
•
If the DHCP server is configured on the NMS, select
DHCP auto
. If not, set this parameter
to
Manual
.
•
The encryption mode must be the same as that on the NMS.
•
After the
Encryption operation CBC
parameter is set, the system automatically restarts.
Exercise caution when performing this operation.