ETP48400-C9A2 Embedded Power
User Manual
A Technical Specifications
Issue 05 (2020-04-07)
Copyright © Huawei Technologies Co., Ltd.
77
Item
Specifications
EMS
Electrostatic discharge
(ESD)
IEC 61000-4-2
Shell port: contact discharge of 6 kV
and air discharge of 8 kV; signal port:
contact discharge of 2 kV
Electrical fast transient
(EFT)
IEC 61000-4-4
AC and DC power ports: 2 kV
Radiated susceptibility (RS)
IEC 61000-4-3
10 V/m field strength
Conducted susceptibility
(CS)
IEC 61000-4-6
Power port: 10 V; signal port: 3 V
Surge immunity
IEC 61000-4-5
AC and DC power ports: 2 kV (8/20
µs) in differential mode, 4 kV (8/20
µs) in common mode
Voltage dips immunity
(DIP)
IEC 61000-4-11
Table A-4
Subrack specifications
Item
Specifications
Cabinet dimensions (H x W x D)
397.3 mm x 482 mm x 330 mm
Weight
≤ 30 kg (excluding rectifiers)
Protection level
IP20
Installation mode
Installed in a 19-inch rack
Cabling
AC cables go in from the bottom, and DC cables go
out from the top.
Maintenance mode
Maintained from the front
Heat dissipation mode
Natural heat dissipation