39
2
EPC4 Connector
1. Material: easy power receptacle (pressfit type) connector, contact terminal, heat shrink tube, and cable
2. Procedure for assembling the easy power receptacle (pressfit type) connector
Strip the jacket off the cable based on the scale on
the equipment.
Scale
Core wire of
the conductor
7.5
+0.5
-0
Ensure that the edge of the core wire is not split.
Insert the conductors into the holes. That is, insert
the red cable connected to the positive pole into
hole 1 and blue cable connected to the negative
pole into hole 2.
Hole for the conductor
The depth of the
conductor into the
hole cannot be less
than 11 mm.
Push back the sliding blocks until they are in
position. Then, check whether the conductors are
secure by gently pulling the cables.
If the conductor slides outward or the core wire of the
conductor is exposed outside the hole for the conductor,
remove the conductor, cut the split wires, and then strip the
jacket and install the conductor again.
Push the sliding block by using a screwdriver until
the in-position mark is completely exposed.
Sliding block
In-position mark
The conductor must be in the
center of the hole
.
The conductor must be
perpendicular to the holes.
The conductor must be in the
center of the hole.
The conductor must be
perpendicular to the hole.
The conductor must be
perpendicular to the hole.
CAUTION