6
GLOBAL ENERGY EFFICIENCY SPECIALIST
Parameter
Min.
Typ.
Max.
Unit
Notes & Conditions
Protection characteristics
Input undervoltage protection
Protection threshold
Recovery threshold
Hysteresis
74
-
5
-
-
-
85
90
-
V AC
V AC
V AC
-
Input overvoltage protection
Protection threshold
Recovery threshold
Hysteresis
295
290
5
-
-
-
310
-
-
V AC
V AC
V AC
-
Output overvoltage protection
-
-
59.5
V
Latch off
Output overcurrent protection
105
-
150
%
Self-recovery
Output short circuit protection
-
-
-
-
Self-recovery;
The module is not damaged even with
long-term short circuits.
Overtemperature protection
Baseplate
Hysteresis
90
5
-
-
-
-
°
C
°
C
Self-recovery;
The overtemperature protection
threshold is obtained by measuring
the temperature of the middle of the
baseplate.
Dynamic characteristics
Overshoot amplitude
Recovery time
-
-
-
-
5
250
%
µs
T
A
= 25
°
C, V
in
= 110/220 V AC;
Current change rate: 0.1 A/
μs;
Load: 25%
–50%–25%;
50%
–75%–50%
Efficiency
100% load
87.0
90.2
-
%
T
A
= 25
°
C, V
in
= 110 V AC; I
out
= 10.5 A
90.0
92.8
-
%
T
A
= 25
°
C, V
in
= 220 V AC; I
out
= 10.5 A
50% load
87.0
90.1
-
%
T
A
= 25
°
C, V
in
= 110 V AC; I
out
= 5.25 A
90.0
92.1
-
%
T
A
= 25
°
C, V
in
= 220 V AC; I
out
= 5.25 A
Other characteristics
Remote On/Off voltage
Low level
High level
0
2.4
-
-
0.8
3.5
V
V
Negative logic
AUX
10
-
14
V
Auxiliary power output. Its output
current is less than 20 mA.
ENA
-
-
-
-
See Enable (ENA).
Electrical Specifications
ADF10S48B