background image

 

- 1 - 

Considerations in Use 

Dear users: 

To use this product correctly and reasonably and avoid unnecessary losses, please read this 
instruction  carefully  before  installation,  use,  circuit  connection,  operation  and  maintenance 
inspection.  This  instruction  introduces  the  structure,  working  principle,  use  conditions, 
installation, commissioning, etc. of the automatic transfer switching device (hereinafter referred 
to as the “transfer switch”), which is conducive to your correct and reasonable use of this product. 
If you have any questions, please consult our company. The user shall be responsible for the 
adverse consequences caused by not operating according to this instruction. 

Attention: 

1. 

Please read this instruction carefully before use, and operate in strict accordance with the 
guidelines. 

2. 

Non-professionals  are  prohibited  from  maintenance  operation,  otherwise  it  will  lead  to 
electric shock or product damage. 

3. 

Before  energizing  or  configuring  the  product,  check  whether  the  specification  of  the 
transfer  switch  meets  the  use  requirements,  and  use  appropriate  voltage  measuring 
equipment to determine the voltage condition. 

4. 

Measure the insulation resistance of the main circuit with a 500 V megger before use (the 
secondary  circuit  must  be  disconnected  during  measurement,  otherwise  the  intelligent 
controller  will  be  damaged),  and  the  resistance  shall  not  be  less  than  1.5  MΩ  at  the 
ambient temperature of 20°C ± 5°C and the relative humidity of 50% ~ 70%. Otherwise, 
the  transfer  switch  shall  be  dried  until  the  insulation  resistance  meets  the  specified 
requirements. 

5. 

This  product  has  been  tested  for  the  dielectric  performance  according  to  the  standard 
before leaving the factory. If the retest is carried out, the controller must be removed to 
avoid damage to the product. 

6. 

Wiring must be carried out according to the phase sequence identification of the incoming 
terminal of the transfer switch body, the phase sequence of the incoming terminals of the 
two  power  supplies  must  be  consistent,  and  the  neutral  wire  must  not  be  mistakenly 
connected to the phase wire. 

7. 

4-pole and 2-pole transfer switches connect the neutral wires of two power supplies to the 
corresponding incoming terminals of "common power supply" and "standby power supply" 
respectively. 3-pole switching devices must have the neutral wires of two power supplies 
connected to the corresponding auxiliary terminals. Do not share the neutral wires, and 
the wiring shall be reliable, otherwise the transfer switch will not work normally. 

8. 

The shell of the transfer switch must be reliably grounded to ensure the safety of operators. 

9. 

Do not install the transfer switch outdoors in damp, direct sunlight, high temperature, large 
vibration  impact  and  conductive  dust,  otherwise  the  service  life  of  the  product  will  be 
shortened or adverse reactions will be caused. 

10.  When  the  transfer  switch  is  in  the  automatic  transfer  state,  do  not  use  the  handle  for 

transfer operation, otherwise the control circuit will be partially damaged. 

11.  In the cases of the failure of common power supply and standby power supply, manual 

closing is prohibited. 

12.  To ensure the reliability of the transfer switch, it is required to conduct the switching test 

regularly  to  confirm  that  the  switch  works  normally  and  ensure  the  continuity  of  power 
supply for important loads. 

13.  Before  the  normal  maintenance  and  troubleshooting  of  the  system  circuit,  all  power 

supplies must be turned off, the switching device shall be switched to the "0" position, and 
then the "No Closing" sign shall be placed in the prominent position for maintenance, so 
as to avoid unnecessary property loss and personal injury. 

14.  When the transfer switch is in maintenance or regular inspection, please commission it in 

the "Manual" mode. 

15.  Products that  are not used  for  a  long  time shall  be moisture-proof and  dust-proof,  and 

must be commissioned according to the specified contents before use to ensure that the 
transfer switch can work normally before being put into operation. 

Summary of Contents for HYT3P Series

Page 1: ...e product please read the instruction carefully and well keep it for future reference Product Certificate This product has passed the inspection and meets the requirements of GB T14048 11 and therefor...

Page 2: ...h body the phase sequence of the incoming terminals of the two power supplies must be consistent and the neutral wire must not be mistakenly connected to the phase wire 7 4 pole and 2 pole transfer sw...

Page 3: ...not exceed 35 C 4 2 The altitude of the installation location shall not exceed 2 000 m 4 3 The relative air humidity at the installation site shall not exceed 50 when the ambient air temperature is 40...

Page 4: ...ectrical life 1 500 1 200 1 000 Use category AC 33B Electrical appliance level PC Contact transfer time 0 6s 20 Transfer operating time 1 3s 10 Return transfer time 1 3s 10 Power off time 0 6s 20 Elec...

Page 5: ...anual transfer switch 7 Sign 8 Grounding screw 9 Indicator light 10 Secondary control line terminal 11 Output terminal 6 2 Controller panel and description Figure 2 Table 2 Product Status 1 2 3 4 Comm...

Page 6: ...voltage Monitoring standby power supply and fault conversion Phase failure voltage loss undervoltage Fire control input DC 24 V Fire control feedback output Indications Common and standby closing indi...

Page 7: ...3P 125 2 224 209 HYT3P 250 4 387 368 170 125 129 8 45 5 HYT3P 250 3 341 323 HYT3P 250 2 295 276 HYT3P 630 4 595 567 255 187 194 13 68 2 HYT3P 630 3 527 499 8 2 4P product main circuit wiring Figure 4...

Page 8: ...d L3 are output terminals A B and C 4 201 is the common power supply neutral wire 5 301 is the standby power supply neutral wire 8 4 2P product main circuit wiring Figure 6 8 4 1 Wiring instruction 1...

Page 9: ...ly is normal 601 and 603 are closed and 602 and 601 are disconnected When the common power supply is abnormal 602 and 601 are closed and 601 and 603 are disconnected 6 501 502 Active input terminal of...

Page 10: ...closed Power on commissioning Adjust the automatic manual switching gear of the transfer switch to the automatic gear first and then energize the two power supplies Commission the product according to...

Page 11: ...nd generator and rated working current of 125 A 11 Ordering Information On the premise that users abide by the use and storage conditions and the product seals are intact if the product is damaged or...

Page 12: ...Address Wenzhou Bridge Industrial Zone Yueqing City Zhejiang Province Service hotline 400 887 5757 Switchboard 0577 62889999 Fax 0577 62885588 Website www huyu com cn...

Reviews: