- 10 - 

Table 5 

Fault 

Cause analysis 

Troubleshooting method 

The indicator light on 
the controller panel is 
not on after power-on 

Loose, falling off or poor contact of power 
supply sampling wire 

Check and connect the 

conductors 

The 3P product neutral wire is not 
connected to the terminal 

Phase failure of power supply 

Check whether the power 

supply voltage is normal 

10  Ordering Information 

10.1  When ordering, please fill in according to Table 6. 

 

Table 6 

Order unit 

 

Order quantity 

 

Order date 

 

Model 

Number 
of poles 

Controller 

code 

Rated working  

current 

Optional 

function code 

Notes 

□HYT3P-125  □2P 

□3P 
□4P 

□ A 
(Economical 
type)  
□ B (Standard 
type) 

□16A  

□20A  

□25A  

□32A 

□40A  

□50A  

□63A  

□80A 

□100A  

□125A 

Type B 

controller 

optional 

□ F 

(Power grid - 

Generator) 

□ W 

(Fire control 

feedback) 

 

□HYT3P-250 

□125A  

□ 140A 

□ 160A  

□ 180A  

□200A  

□ 225A 

□ 250A 

□HYT3P-630 

□3P 
□4P 

□250A 

□ 315A 

□ 350A 

□ 400A 

□ 500A 

□ 630A 

Example: 

HYT3P-125/4 B F W 125 A indicates a 4-pole automatic transfer switching equipment with 
automatic charge and automatic recovery of power grid and generator, and rated working current 
of 125 A. 

11  Ordering Information 

On the premise that users abide by the use and storage conditions and the product seals are 
intact,  if  the  product  is  damaged  or  cannot  be  used  normally  due  to  manufacturing  quality 
problems  within  18  months  from  the  production  date  of  the  product,  our  company  will  be 
responsible for the repairing or replacement free of charge. If the warranty period expires, users 
shall pay for the repair. However, if the damage is caused by the following circumstances, the 
fees for repair still sha be charged even within the warranty period: 
(1).  Misuse, self-modification, improper maintenance, etc. 
(2).  Use beyond the standard specification requirements. 
(3).  Falling, damage during transportation, etc. after purchase. 
(4).  Earthquake, fire, lightning strike, abnormal voltage, other natural disasters and secondary 

disasters, etc. 

In case of any questions, please contact the dealer or our customer service department. 
 

Dear customers: 

To protect our environment, please recycle the product or its components when the product is 
scrapped. For materials that cannot be recycled, please handle them properly. Thank you very 
much for your cooperation and support. 

 

Summary of Contents for HYT3P Series

Page 1: ...e product please read the instruction carefully and well keep it for future reference Product Certificate This product has passed the inspection and meets the requirements of GB T14048 11 and therefor...

Page 2: ...h body the phase sequence of the incoming terminals of the two power supplies must be consistent and the neutral wire must not be mistakenly connected to the phase wire 7 4 pole and 2 pole transfer sw...

Page 3: ...not exceed 35 C 4 2 The altitude of the installation location shall not exceed 2 000 m 4 3 The relative air humidity at the installation site shall not exceed 50 when the ambient air temperature is 40...

Page 4: ...ectrical life 1 500 1 200 1 000 Use category AC 33B Electrical appliance level PC Contact transfer time 0 6s 20 Transfer operating time 1 3s 10 Return transfer time 1 3s 10 Power off time 0 6s 20 Elec...

Page 5: ...anual transfer switch 7 Sign 8 Grounding screw 9 Indicator light 10 Secondary control line terminal 11 Output terminal 6 2 Controller panel and description Figure 2 Table 2 Product Status 1 2 3 4 Comm...

Page 6: ...voltage Monitoring standby power supply and fault conversion Phase failure voltage loss undervoltage Fire control input DC 24 V Fire control feedback output Indications Common and standby closing indi...

Page 7: ...3P 125 2 224 209 HYT3P 250 4 387 368 170 125 129 8 45 5 HYT3P 250 3 341 323 HYT3P 250 2 295 276 HYT3P 630 4 595 567 255 187 194 13 68 2 HYT3P 630 3 527 499 8 2 4P product main circuit wiring Figure 4...

Page 8: ...d L3 are output terminals A B and C 4 201 is the common power supply neutral wire 5 301 is the standby power supply neutral wire 8 4 2P product main circuit wiring Figure 6 8 4 1 Wiring instruction 1...

Page 9: ...ly is normal 601 and 603 are closed and 602 and 601 are disconnected When the common power supply is abnormal 602 and 601 are closed and 601 and 603 are disconnected 6 501 502 Active input terminal of...

Page 10: ...closed Power on commissioning Adjust the automatic manual switching gear of the transfer switch to the automatic gear first and then energize the two power supplies Commission the product according to...

Page 11: ...nd generator and rated working current of 125 A 11 Ordering Information On the premise that users abide by the use and storage conditions and the product seals are intact if the product is damaged or...

Page 12: ...Address Wenzhou Bridge Industrial Zone Yueqing City Zhejiang Province Service hotline 400 887 5757 Switchboard 0577 62889999 Fax 0577 62885588 Website www huyu com cn...