Table 7 Number of operation cycles 

Shell frame level 

rated current Inm 

(A) 

Number of 

operation cycles 

per hour 

Number of operation cycles 

Energizing 

De-energizing 

Total times 

125 

120 

1,500 

8,500 

10,000 

250 

120 

1,000 

7,000 

8,000 

400 

60 

1,000 

4,000 

5,000 

630 

60 

1,000 

4,000 

5,000 

 

6. Electric operating mechanism 

When the electric operating mechanism is used for the earth leakage circuit 

breaker, reliable closing and opening of the circuit breaker shall be ensured 

at any voltage between 85% and 110% of the rated control power supply 

voltage. 

7. Shunt trip 

When the power supply voltage is equal to any voltage between 70% and 

110% of the rated control power supply voltage, the circuit breaker can be 

reliably interrupted by operating the shunt trip. 

8. Undervoltage release 

When the power supply voltage drops to 70% ~ 35% of the rated power 

supply voltage, the undervoltage release shall  act to interrupt the earth 

leakage circuit breaker. When the power supply voltage is lower than 35% 

of the rated power supply voltage, the undervoltage release shall prevent the 

earth leakage circuit breaker from closing. When the power supply voltage is 

equal to or greater than 85% of the rated power supply voltage, reliable 

closing of the earth leakage circuit breaker shall be ensured. 

9. LB earth leakage alarm module (see Figure 1) 

The HYM1LB Earth Leakage Circuit Breaker is plugged with LB earth 

leakage alarm module on the right side of the circuit breaker. Terminals P1-

P2 of this module are externally connected with AC 400 V or AC 230 V power 

supply. When earth leakage occurs in the main circuit of the earth leakage 

circuit breaker and IΔ ≥ IΔn, the earth leakage circuit breaker does not trip, 

the relay in the alarm module acts, and the terminals S1, S2 and S3 are 

internally connected with relay contacts to send out alarm signals. 

 

Figure 1  

Wiring diagram of the LB earth leakage alarm module 

Where S2-S3 are normally-closed contacts and S1-S2 are normally-open 

contacts: 

A.  When I

 I

n, the earth leakage indicator light is not on, and S2-S3 is 

closed and S1-S2 is open. 

LB earth 

leakage 

alarm 

module 

Contact 

capacity 

Summary of Contents for HYM1L Series

Page 1: ...e read the instruction carefully and well keep it for future reference Product Certificate This product has passed the inspection and meets the requirements of GB T 14048 2 and therefore is allowed to...

Page 2: ...h alarm contact shunt trip undervoltage release auxiliary contact handle rotation operating mechanism electric operating mechanism and other accessories and can adopt the wiring in front of the plate...

Page 3: ...erprise code Note 1 2P is denoted by 2 3P is denoted by 3 and 3P N and 4P are denoted by 4 2 The type of neutral pole N pole of the 4 pole circuit breaker is divided into Type A The N pole is not equi...

Page 4: ...nstantaneous release and 3 indicates thermal electromagnetic complex release The last two digits indicate the internal accessory code or 00 if there is no accessory In HYM1L 400 and 630 the auxiliary...

Page 5: ...sidual short circuit making breaking capacity I m kA Flashover distance mm HYM1L 125L 230 2 16 20 25 32 40 50 63 80 100 125 35 22 Type A Type AC 50 100 200 300 500 1 2 I n 1 4 Icu 50 400 3 4 HYM1L 125...

Page 6: ...ld state Conventional tripping current 1 30In lh 2h Thermal state 3 See Table 6 for the interruption characteristics of inverse time operation of the earth leakage circuit breaker for motor protection...

Page 7: ...upply voltage is lower than 35 of the rated power supply voltage the undervoltage release shall prevent the earth leakage circuit breaker from closing When the power supply voltage is equal to or grea...

Page 8: ...iary power supply Us Whether S2 S3 and S1 S2 are closed in each working state can be detected by a multimeter 10 See Table 8 and Table 9 for the cross section area of connecting conductor of earth lea...

Page 9: ...ircuit Figure 2 Principle of operation VI Outline and Installation Dimensions see Figure 3 and Table 10 Table 10 Outline and installation dimensions Model Number of poles Outline dimensions max nm Ins...

Page 10: ...megger b Measure the insulation resistance between terminals 1 2 3 4 and 5 6 when the earth leakage circuit breaker is switched off c Measure the insulation resistance between the terminals of the mai...

Page 11: ...electric shock caused by contact with two load lines at the same time and therefore users shall pay attention to the electricity safety 2 Do not test the device by means of short circuit between phas...

Page 12: ...ling damage during transportation etc after purchase 4 Earthquake fire lightning strike abnormal voltage other natural disasters and secondary disasters etc In case of any questions please contact the...

Reviews: