Table 2-1.1:
HTW
-V5(7)WD2N8 specifications
1
(continued)
kW
5
Model name
MOP
A
20.0
20.0
20.0
MCA
A
14.1
14.1
14.1
Water side heat exchanger
Plate type
Water pump
Pump head
m
6.0
6.0
6.0
Expansion tank
Volume
L
2.0
2.0
2.0
Refrigerant
Type
kW
R32
Charge
kg
2.0
Throttle type
Electronic expansion valve
Backup electric heater
Standard internal
kW
-
-
-
Optional
kW
3
3
3
Output steps
1
1
1
Power supply
V/Ph/Hz
220-240/1/50
Sound power level
8
dB(A)
61
Net dimensions (W×H×D)
mm
1210×945×402
1210×945×402
1404×1414×405
Packed dimensions (W×H×D)
mm
1500×1140×450
1500×1140×450
1475×1580×440
Net/Gross weight
kg
92/111
99/117
99/117
Water piping connections
mm
1’’ Male BSP
Ф25 Female BSP
Ф32 Female BSP
Safety valve set pressure
MPa
0.3
0.3
0.3
Total water volume
L
2
2
2
Operating temperature
range
Cooling
⁰C
-5 to 43
Heating
⁰C
-25 to 35
DHW
⁰C
-25 to 43
LWT range
Cooling
⁰C
5 to 25
Heating
⁰C
25 to 60
DHW
⁰C
40 to 60
Abbreviations:
MOP: Maximum overcurrent protection
MCA: Minimum circuit amps
DHW: Domestic hot water
EWT: Entering water temperature
LWT: Leaving water temperature
Notes:
1. Relevant EU standards and legislation: EN14511:2013; EN14825:2013; EN50564:2011; EN12102:2011;
(EU) No 811/2013; (EU) No 813/2013; OJ 2014/C 207/02
2. Outdoor air temperature 7⁰C DB, 85% R.H.; EWT 30⁰C, LWT 35⁰C.
3. Outdoor air temperature 7⁰C DB, 85% R.H.; EWT 40⁰C, LWT 45⁰C.
4. Outdoor air temperature 7⁰C DB, 85% R.H.; EWT 47⁰C, LWT 55⁰C.
5. Outdoor air temperature 35⁰C DB; EWT 23⁰C, LWT 18⁰C.
6. Outdoor air temperature 35⁰C DB; EWT 12⁰C, LWT 7⁰C.
7. Seasonal space heating energy efficiency class tests in average climate conditions.
8. Sound power level is the maximum value tested under the three conditions of Notes1, Notes3 and Note5..
64
7
HTW-V7WD2N8
HTW-V5WD2N8
21