LP-517 Rev. 000 Rel. 019 Date 7.21.20
10
Figure 3 - Correct and Incorrect Leveling
Figure 4 - Recommended Service Clearances
NOTE:
In multiple boiler installations, ensure an 18” minimum clearance is maintained between boilers.
Precautions
If the boiler is located in a residential garage, per ANSI Z223.1:
• Install the boiler burner and ignition devices a minimum of 18” above the floor of the garage. This will ensure the burner and ignition
devices are well off the floor.
• When raising the boiler ensure the entire bottom and fully filled weight of the boiler are fully supported.
• Locate or protect the boiler so it cannot be damaged by a moving vehicle.
E. Residential Garage and Closet Installations
CAUTION
Check with your local Authority Having Jurisdiction for requirements when installing the boiler in a garage or closet. Please read the entire
manual before attempting installation. Failure to properly take factors such as venting, piping, condensate removal, and wiring into account
before installation could result in wasted time, money, and possible property damage and personal injury.
The space must be provided with combustion / ventilation air openings correctly sized for all other appliances located in the same space
as the boiler. The boiler cover must be securely fastened to prevent the boiler from drawing air from the boiler room. This is particularly
important if the boiler is in a room with other appliances. Failure to comply with the above warnings could result in substantial property
damage, severe personal injury, or death.