PV-ISOTEST
EN - 22
10. If “
Ri(-)
≥
Lim
”, the instrument shows the message “
OK
”,
to indicate the
positive
result of measurement.
If the measuring time is
≥
60s, the instrument shows on
the display the value of parameter
DAR
(Dielectric
Absorption Ratio) (see § 11.2).
If the measuring time is
≥
600s, the instrument shows on
the display both the value of parameter
DAR
(Dielectric
Absorption Ratio) and the value of parameter
PI
(Polarization Index) (see § 11.1).
Press the
SAVE
key to store the test result in the
instrument’s memory (see § 7.1) or the
ESC/MENU
key
to exit the screen without saving and go back to the main
measuring screen.
M
15/10 – 18:04
V t e s t ( - ) 1 5 4 0
V
R i ( - ) > 1 0 0
M
T i m e
6 0 0
s
D A R 1 . 4 1 P I
1 . 0 2
V P N
V P E
V N E
0 V
0 V
0 V
OK
TMR 1500V 1.00M
700s
MODE
Vtest. Lim. Time