JUPITER
IT - 28
Tripping time in manual mode (test current I
n)
Fig. 35: Tripping time in manual mode at I
n
10. The correct measurement result is shown on the display (see Fig. 35
–
left side) with
indication
“
OK
”
11. The correct measurement result is shown on the display (see Fig. 35
–
right side) with
indication
“
NOT OK
”
. The buzzer gives a short continuous sound
Tripping time in manual mode (test current 5xI
n)
Fig. 36: Tripping time in manual mode at 5xI
n
10. The correct measurement result is shown on the display (see Fig. 36
–
left side) with
indication
“
OK
”
11. The wrong measurement result (
tripping time > 40ms)
is shown on the display (see
Fig. 36
–
right side) with indication
“
NOT OK
”
. The buzzer gives a short continuous
sound
RCD tripping current
Fig. 37: RCD tripping current
10. The correct measurement result is shown on the display (see Fig. 36
–
left side) with
indication
“
OK
”
. Notice the presence of tripping time on the top of the display on the
right side.
11. The wrong measurement result is shown on the display (see Fig. 36
–
left side) with
indication
“
NOT OK
”
(tripping current > 33mA)
. The buzzer gives a short continuous
sound