HT2055
EN - 11
5.1.4 Default settings
This section permits to restore the default value (factory) of measurement parameters and
limits set on the instrument
Fig. 10: Initial settings screen
1. Press
or
keys to enter Settings menu
2. Select the item “Initial Settings” with the
or
keys and press
TEST
key
3. Select the “NO” or “YES” options with the
or
keys and confirm with
TEST
4. Press
ESC
key to exit and go back to the previous screen
The default values are the following:
Language
English
Contact and Step voltage
I
GEN
= 10A
I
FLT
= 1kA
R
INP
= 1M
Ω
U
LIM
= 50V
5.1.5 Time/Date settings
Fig. 11: Time/Date settings screen
1. Press
or
keys to enter Settings menu
2. Select the item “Set Date/Time” with the
or
keys and press
TEST
key
3. Use the
,
,
and
keys to set the date/time and confirm with
TEST
4. Press
ESC
key to exit and go back to the previous screen
5.2 MESSAGES AT DISPLAY
The below messages (icons) can be displayed on the meter unit:
The meter and the station are not synchronized
Measurement is running
Results can be stored
Measurement result is within pre-set limits (PASSED)
Measurement result is out of pre-set limits (FAILED)