PQA819 - PQA820
EN – 21
AC Power/Energy – (Vmeas > 200V, Pf=1)
Clamp FS [A]
Range [W] [Wh]
Resolution [W] [Wh]
Accuracy
1< FS
10
0.000k
9.999k
0.001k
(0.7
rdg + 3W/Wh)
10.00k
99.99k
0.01k
(0.7
rdg+30W/Wh)
10< FS
200
0.00k
99.99k
0.01k
(0.7
rdg+30W/Wh)
100.0k
999.9k
0.1k
(0.7
rdg+300W/Wh)
200< FS
1000
0.0k
999.9k
0.1k
(0.7
rdg+0.3kW/kWh)
1000k
9999k
1k
(0.7
rdg+3kW/kWh)
Vmeas = Voltage in which the power is measured
Power factor and Cos
Range
Resolution (°)
Accuracy (°)
0.20
0.50
0.01
0.6
0.50
0.80
0.7
0.80
1.00
1.0
Voltage / Current harmonics (recording only for PQA820)
Range
Max resolution
Accuracy
DC
25
th
0.3V / 0.1%FS clamp
(5.0
rdg + 2dgt)
26
th
33
th
(10
rdg + 2dgt)
34
th
49
th
(15
rdg + 2dgt)
The harmonics will be zeroed under the following conditions
DC: if the value of DC <0.5% of the value of the fundamental or if the DC value < 0.5% of the FS clamp
1st harmonic: if the value of the 1st harmonic <0.5% of the FS clamp
2nd
49th harmonic: if the value of harmonic <0.5% of the value of the fundamental or if <0.5% of the FS clamp
11.2. REFERENCE GUIDELINES
Safety: IEC/EN
61010-1
Quality of voltage supply:
EN50160 (voltage / THDV%) and harmonics (PQA820)
Insulation: double
insulation
Pollution level:
2
Max. height of use:
2000m (6562ft)
Measurement category:
CAT IV 300V AC (to ground), Max 460V between inputs
11.3. GENERAL CHARACTERISTICS
Mechanical characteristics:
Dimensions (L x W x H):
245 x 210 x 110mm (10 x 8 x 4in)
Weight: 1.5kg
(3lv)
Power supply
Internal power supply:
rechargeable battery (battery life approx.1 hour)
External power supply:
Ing. Red-Yellow: 100
415V, 50/60Hz
45mA@100V, 30mA@230V, 20mA@415V
Measurement, memory and Interface
Number of samples per period:
128, (64 in “Real Time” connection)
Max. simultaneous recordable parameters:
383 (PQA820), 44 (PQA819)
Max. recordable voltage anomalies:
65530 (PQA820)
Integration period:
5, 10, 30s, 1, 2, 5, 10, 15, 60min
Recording autonomy:
> 30 days (@ IP = 10 minutes) (PQA820)
> 230 days (@ IP = 15 minutes) (PQA819)
Memory: 8Mbyte
Communication interface (PC/Tablets):
USB (PC only) / WiFi
11.4. ENVIRONMENT
11.4.1. Environmental conditions for use
Reference temperature:
23°C ± 5°C (73°F ± 41°F)
Operating temperature:
0°C ÷ 40 °C (32°F ÷ 104°F)
Allowable relative humidity:
<80%HR
Storage temperature:
-10°C ÷ 60°C (14°F ÷ 140°F)
Storage humidity:
<80%HR
Instrument complies with Directive 2006/95/EEC (LVD) and EMC Directive 2004/108/EEC requirements
11.5. ACCESSORIES
Use only the supplied and optional accessories included in the enclosed packing list