INTRODUCTION

This manual covers the installation of the heat interface unit and the relative applicable instructions. These

must be followed to ensure the proper and trouble-free operation of the heat interface unit. You will also

find general technical details and information about maintenance, any errors occurring and their possible

causes. This document forms part of the heat interface unit and must be kept with the interface unit.

APPLICATION

The interface unit is used in collective heat distribtuion systems. This interface unit is suitable for both

heating and preparing domestic hot water. The water that runs through the different systems connected to

the interface unit needs to meet the water quality standards mentioned in document 53261 “Requirements

on water quality for Heat Interface Units for District Heating systems”. The interface unit needs to suffi ce

with the IWUN guidelines 06283 and 06285 and the NEN2768 standard.

STATUS INDICATION LED LIGHT OF THE INTERFACE UNIT

General

Flashing blue  

 

 

 

: Interface unit is in hot domestic water position

Flashing red  

 

 

 

: Interface unit failure

Continuously white (only for heat supplier)  

: Interface unit is in service mode

No LED    

 

 

 

: Interface unit off

Interface unit with room thermostat connection cable and with priority

Flashing green slowly (approx. once per second)   : Interface unit in rest position; there is no heat demand

 

 

 

 

 

  and the CH control valve is closed.

Flashing green quickly (approx. twice per second)   : Interface unit in CH position; there is heat demand and

 

 

 

 

 

  the CH control valve is open.

Interface unit without room thermostat connection cable or priority switching

Flashing green slowly (approx. once per second)   : Interface unit in rest or CH position.

OPERATION

Central heating system

The interface unit is fitted with a differential pressure regulator that keeps the differential pressure

constant throughout the CH installation. The differential pressure ensures continuous flow of heat from the

district heating network through the CH installation.

Room thermostat connection

A (smart) room thermostat can optionally be connected to the heat interface unit. The interface unit will

then respond to heat demand from the room thermostat. The connection of a room thermostat is not

necessary for the proper operation of the interface unit. A conductor is connected to the thermostat

connection cable ex-works (default). This conductor ensures a closed contact and therefore ensures heat

demand at the interface unit.

         Note!

Only (smart) on/off room thermostats can be connected which have a potential-free contact or the

Honeywell round on/off (T87G2014) type thermostat with power-stealing technology. Thermostats without

a potential-free contact and/or not of the on/off type are explicitly not allowed.

                    Note!

High temperatures of parts in the interface unit, pipework and radiators

The interface unit is designed for district heating networks with water temperatures to 95 ºC. The pipework

and parts in the interface unit as well as pipework and radiators in the CH installation can reach this

temperature. Contact can result in burns.

Summary of Contents for EcoAdvance Compact

Page 1: ...EcoAdvance Compact EcoAdvance Compact Save this manual with the interface unit Art nr 54324 Rev A 13 02 2020 Changes and misprints reserved INSTALLATION USER MANUAL ...

Page 2: ...Electric drill Manual processing Abbreviations DHW Domestic hot water C Temperature in degrees Celsius CH Central heating system Hz Unit for frequency 1 second pH Acidity g kg Unit for weight in grams Pa kPa Unit for pressure in Pascal mm Unit for distance in millimeter Wh kWh Unit for energy in watt hours Unit for length in inch W kW Unit for power in watt VAC Unit for alternating voltage in Volt...

Page 3: ...ns 6 Maintenance and inspection 7 Technische specificaties 8 Heat exchanger 40 plates 9 Delivery range 11 Additional items required 11 Dimensions 11 Installation 12 Room thermostat optional 16 Commisioning 17 Cover sealing 18 Errors end user 19 Errors installer 20 Guarantee 21 EC Declaration of conformity 23 ...

Page 4: ... 9 LED indication 10 Temperature sensor district heating network 11 CH control valve 12 Temperature sensor district heating network supply 13 Nipple for temperature sensor for heat meter 14 Flow sensor domestic water 15 Spool piece for heat meter 16 Differential pressure regulator 8 9 10 11 16 1 2 3 4 13 12 15 14 5 6 7 A B C D E F A Primary supply B Primary return C Domestic Hot Water D Domestic C...

Page 5: ...pply Domestic cold water District heating network supply CH return Spool piece L 110mm Electronic control unit 2 13 7 6 5 10 12 15 14 16 11 9 Connection thermostat ON OFF Service cable District heating network return Optional Domestic hot water ...

Page 6: ...reen quickly approx twice per second Interface unit in CH position there is heat demand and the CH control valve is open Interface unit without room thermostat connection cable or priority switching Flashing green slowly approx once per second Interface unit in rest or CH position OPERATION Central heating system The interface unit is fitted with a differential pressure regulator that keeps the di...

Page 7: ...a power outage during hot water tapping or in a situation where there is no heat demand from the connected room thermostat the CH control valve remains in the closed position This can result in the cooling of the CH installation Installation conditions With the installation of the interface units account must be taken of the current and applicable Buildings Regulations safety requirements for CH i...

Page 8: ...he heat supply for domestic water and CH The jacket can be cleaned with a damp cloth Under no circumstances use solvents for example cleaning spirit methylated spirits etc Note The interface unit contains electrical components 24 V direct current These components are not splashproof and must be kept dry at all times DURING ABSENCE OR HOLIDAYS Do not pull the plug out of the plug socket During long...

Page 9: ...estic hot water Central Heating supply Central Heating return Heatmeter in supply Temperature sensor heatmeter Electrical power supply Electrical power consumption per year kWh Height mm Width mm Depth mm Weight kg 3 Type on off thermostats with potential free contacts or Honeywell round on off T87G2014 thermostat with powerstealing 16 50 25 Dimensions 475 300 246 1 Performance HIU is dependent on...

Page 10: ...r temperature 55 C old domestic water temperature 10 C Domestic water flow litres minute Pressure drop tapping side kPa Pressure drop tapping side Power kW Power kW Pressure drop tapping side over interface unit Power kW Domestic water flow litres minute District heating network 65 C District heating network 70 C District heating network 80 C Power kW District heating network return temperature Di...

Page 11: ...Pressure drop district heating network kPa Power kW Domestic water flow litres minute District heating network flow litres minute Power kW 0 10 20 30 40 50 60 70 80 0 0 2 5 5 0 7 5 10 0 12 5 15 0 17 5 20 0 0 2 4 6 8 10 12 14 16 18 20 District heating network 65 C District heating network 70 C District heating network 80 C Power kW District heating network 65 C District heating network 70 C Distric...

Page 12: ... 80 40 40 300 250 75 100 75 HSF EcoAdvance Compact 15 Leveromvang Maatvoering 1x 230 V 14 22 24 30 mm Torx 25 220 195 140 80 175 75 25 40 300 250 485 495 Benodigdheden 170 65 65 60 80 80 40 40 300 250 75 100 75 HSF EcoAdvance Compact 15 Leveromvang Maatvoering 1x 230 V 14 22 24 30 mm Torx 25 220 195 140 80 175 75 25 40 300 250 485 495 170 65 65 60 80 80 40 40 300 250 75 100 75 Additional items req...

Page 13: ...rict heating supply 3 Domestic cold water 4 Domestic hot water 5 CH supply 6 CH return HSF EcoAdvance Compact 16 Installatie 1 2 1 2 1 Warmtedistributienet aanvoer 2 Warmtedistributienet retour 3 Warm tapwater 4 Koud tapwater 5 CV aanvoer 6 CV retour 6x 1 2 3 2 1 3 5 4 6 3 1 2 ...

Page 14: ...13 EcoAdvance Compact 3 4 1 2 30 mm 6x 2 1 6x ...

Page 15: ...nce Compact 5 mm 30 mm 3 24 mm 22 mm 1 14 mm Option 1 22 mm 2 Option 2 Note Spool piece must be removed and replaced by heat meter or steel spool piece Art Nº 44452 Contact your supplier 3 3 1 2 option 1 option 2 ...

Page 16: ...15 EcoAdvance Compact 1 2 2 option 1 Connection M10 x 1 BN option 2 Connection BN 30 mm 2 1 6 ...

Page 17: ...move the conductor only when a thermostat is used 2 Connect the room thermostat cable with an isolated conductor to the room thermostat sold separately CAUTION The unit can optionally be connected to a room thermostat For eligable types of thermostats see chapter Technical data 1 1 2 ...

Page 18: ... C should now be flashing green 6 Gradually open the district heating network supply D and check the unit for leaks 7 Gradually open the district heating network return E and check for leaks 8 Gradually open the CH supply F 9 Deaerate the system Start at the lowest and end at the highest radiator or bleed point 10 Gradually open the CH return G 11 Check there is heat in the system 12 Gradually ope...

Page 19: ...18 EcoAdvance Compact Cover sealing 2 torx 25 1 2 1 ...

Page 20: ...cal position If not open the valves 2 Check whether the plug of the appliance is inserted in the plug socket 230 V If not insert the plug in the plug socket 3 Check whether the radiator valves are open If not open the radiator valves 4 Set your thermostat higher than the ambient temperature 5 Problem solved If not contact your heat supplier Domestic water does not heat up 1 Check whether the valve...

Page 21: ...acket closed Open all valves on the pre fix bracket Strainer is blocked Clean all strainers Differential pressure district heating network too low Check differential pressure Supply temperature district heating network too low Check supply temperature Adaptor not in wall socket Place adaptor in wall socket Adaptor cable connector not in proper position Push the connection firmly into place Defecti...

Page 22: ...stem Electronic DHW system Model EcoAdvance Compact 5 Manufacturer HSF B V 6 Address Marketing 23 Duiven The Netherlands 7 This equipment or protective system and any acceptable variation thereto is specified in the schedule to this declaration and the documents therein referred to 8 The examination and test results are recorded in Technical file no 281A Compliance with the Essential Requirements ...

Page 23: ...22 EcoAdvance Compact ...

Page 24: ...23 EcoAdvance Compact ...

Page 25: ...24 EcoAdvance Compact ...

Page 26: ...25 EcoAdvance Compact ...

Page 27: ...26 EcoAdvance Compact ...

Page 28: ...27 EcoAdvance Compact ...

Reviews: