Installation & Commissioning 

Power & RS485 

 

  This is an RS485 network device designed for indoor use, mounted in a dry electrical panel. 

Ideally it should be mounted to the panel backplane in a horizontal position (RJ11 sockets on 
the lower side and communications ports on the upper side) 

 

  Each 24Vac power supply transformer should have the neutral (24Vac N) connection grounded 

at the electrical panel earth connection to ensure the device grounding is at the same potential 
as the network master’s grounding 

 

  Where more than one device is connected to a common transformer ensure that the 24Vac 

phasing is the same to each device (‘A’ connects to ‘A’, ‘N’ connects to ‘N’ in all cases) 

 

  If the red comms light adjacent to the RS485 terminals emits an obvious flash every time 24Vac 

power is applied to the device then the micro-processor may be corrupted. The micro processor 
should be replaced 

 

  RS485 multi-drop cable should be used for the network connections, complete with end of line 

terminating resistors (120Ω). Belden 9841 or equivalent is recommended. The recommended 
cable is a low capacitance twisted pair with braid and foil screen 

 

  The RS485 cables should be terminated directly at each device in a daisy-chain configuration, 

avoiding ‘laterals’ or ‘spurs’ 

 

  The RS485 screen should be connected at the network master’s ground terminal. The incoming 

and outgoing screen at each device should be continuously connected via the S terminal of the 
device (note that the device’s S terminal has no electrical connection to the device, it merely 
acts as a junction terminal for the purpose of screen continuity) 

 

  The RS485 cable should avoid cable routes that run with power cables. Where the RS485 

cable must cross power cables then they should cross at 90° avoiding parallel runs beside 
power cables  

 

  Prior to connection of the slave devices to the RS485 network check that no AC voltage is 

present. Double check the network for short circuits between the twisted pair cores and 
between the cores and the screen. Ensure continuity of the twisted pair cores and the screen 

 

  Check the network master’s +/- terminals for correct voltages to ground (approx. 2.5Vdc) and 

connect the RS485 network cable to the network master’s RS485 port  

 

  At each device assign an individual address and the baud rate specific to the network. Write the 

changes, eXit the terminal application and remove the HPECOM cable 

 

  Verify network voltage at the RS485 connector (b/- and ground) and connect to the 

device. Communication can be verified by flashing of the red comms LED adjacent the 3 
terminal RS485 connector). Frequency of comms LED flash is baud rate dependant. At higher 
baud rates the LED flash may not be obvious, the LED appearing to be continuously on 

 

  Where a network runs between buildings and zero earth potential difference between individual 

panel 24Vac power supplies cannot be guaranteed, we recommend that a repeater be used to 
provide isolation of the sections of the network having differing earth potential 

 

Summary of Contents for BACnet HPE-MRBN

Page 1: ...et MS TP devices HVAC Controllers PMAC770 electricity meters c w BACnet module Sontex SC531 chilled hot water energy integrators c w BACnet module Belimo energy Valves Belimo energy valves should have dedicated gateway with System Vendor ID 423 SV 423 set in the gateway Other BACnet devices may share a gateway with default SV 0 setting Feature Summary Modbus RTU RS485 slave port BMS port BACnet MS...

Page 2: ...gs 6 Connecting at 76800 Baud Rate 6 Saving HyperTerminal Settings 6 BREAK IN TO TERMINAL MODE 6 MODBUS CONFIGRATION COMMANDS 7 BACNET CONFIGURATION COMMANDS 8 DATA BASE MAPPING TOOL 9 TERMINAL OPERATION 10 DOWNLOAD TEXT FILE 10 ENABLE BACNET MS TP PORT 11 VERIFY BACNET NETWORK COMMUNICATION 11 INSTALLATION COMMISSIONING 12 POWER RS485 12 CONNECTIONS 13 DIMENSIONS 13 TECHNICAL DATA 14 ORDERING INF...

Page 3: ...e 250 registers relating to the BACnet network devices data objects being read Long Integer Registers 4 6 8 502 Modicon Register Addresses using F03 Holding Register as example 40005 40007 40009 40503 IEEE Floating Point Registers 1004 1006 1008 1502 Modicon Register Addresses using F03 Holding Register as example 41005 41007 41009 41503 Write Relinquish The gateway operates on the BACnet side wit...

Page 4: ...manual available to assist with BACnet Object settings The gateway data base consists of 250 Modbus registers each configured with a target BACnet object s data 1 BACnet device address where the object resides MS TP Node address MAC 2 Object type BI BV BO AI AV AO MI MV MO 3 Object Instance object number Separately the BACnet network baud rate and Maximum Master value must be set The gtaeway is ge...

Page 5: ...or from Shade Blue are recommended The USB driver for the HPECOMU may be found on our web site The following settings reflect HyperTerminal Please contact us if you require assistance setting up Indigo HyperTerminal Settings For successful communication between HyperTerminal and the device initial Properties setup of HyperTerminal should be as per the screen prints below Connect to Comm Configurat...

Page 6: ...allow later terminal communication a device set with 76800 baud will operate at 9600 baud for the first 5 seconds after a power up If no attempt to connect the terminal at 9600 baud is made within 5 seconds of a power up then the device will automatically switch to 76800 for normal network operation Saving HyperTerminal Settings For ease of connection it is recommended to save the HyperTerminal se...

Page 7: ...57600 76800 Example 1001 38400 After changing comm speed it will be necessary to reconnect with HyperTerminal at the new comm speed to save write the change Zero the Reset counters 1 0 All Reset counters are zeroed Factory diag In order as displayed Rx timeout Tx timeout Hardware reset Zero the BACnet comms error counter 2 0 BACnet comms error counter is reset Example 2 0 Zero the M Bus comms erro...

Page 8: ... entered one by one Delete current point data base DE followed by 10000 1 Any configuration of point 4 502 is deleted Download of a text file with new data base will delete an old existing data base as a matter of course Enable BACnet subnet communication E Toggles Enabled Disabled of M Bus Subnet communication Default Disabled to allow easy configuration when no devices are connected Always Enabl...

Page 9: ...uest or by download from www hrw hk Resources Tools you can use our the HPE MRBN mapping Tool for creation of a table of data base settings which can be downloaded to the gateway as a text file txt As well as the generic BACnet mapping tool we also have Belimo device specific mapping tools available on request Copy the Download Table lines from the tool to Notepad text file and save for download t...

Page 10: ... entering the required settings Note that after changing the Modbus baud rate the terminal mode baud rate is also changed so reconnect HyperTerminal at the newly set baud rate and then Write W the new setting Download Text File Enter DE The display will indicate that the existing data base is being blanked and now Ready to receive data base text file While in the Ready state navigate to the text f...

Page 11: ...et MS TP communication and enter W to write the enabled state so that it will still be enabled after a power failure Note To disable enter E again to toggle from enabled to disabled state Verify BACnet Network Communication In terminal mode any scanning of the BACnet network will only occur after the data based points are added to the Log list 1 Enter L to place all points on log 2 Enter X to eXit...

Page 12: ...oing screen at each device should be continuously connected via the S terminal of the device note that the device s S terminal has no electrical connection to the device it merely acts as a junction terminal for the purpose of screen continuity The RS485 cable should avoid cable routes that run with power cables Where the RS485 cable must cross power cables then they should cross at 90 avoiding pa...

Page 13: ...1 Manual 170912 E O E Subject to change without notice Page 13 of 15 Connections Dimensions If using HDA0002 DIN rail adapter brackets the overall depth from the gear plate to the front surface of the device is 45 5mm ...

Page 14: ...e for control panel mounting Standard package 40 units per carton Accessories HDA0002 DIN rail adapter brackets factory fitted HPECOMU Configuration cable USB Other HP_MR Series Devices HPC0662MR Universal Controller 12 Point Modbus RTU 24Vac HPC8884MR Universal Controller 28 Point Modbus RTU 24Vac HPD0440BNMR Network HMI Universal Ctrl Scheduler Modbus RTU gateway 8 Point BACnet MS TP 24Vac HPD04...

Page 15: ...HRW HPE MRBN V401 Manual 170912 E O E Subject to change without notice Page 15 of 15 Notes ...

Reviews: