HRS Hevac Ltd AquaModule AMB
Installation, Operating & Instruction Manual
14.1 Open the control box
Remove the front panel by turning the lock button counter clockwise and
lift the cover.
Picture 19
Unscrew the two screws in bottom and lift up the black panel.
Picture 20
14.2 Change fuses
The control box is fitted with a set of fuses to protect the different components against overload.
Extra fuses are included in the control box for quick servicing.
The service work must be carried out by an authorized service technician.
Turn off the power supply before starting to work.
Picture 21
F5
Fuse F5
1
Led 1, lit when pump P1 is power supplied
F1
Fuse F1
2
Led 2, lit when pump P2 is power supplied
F2
Fuse F2
3
Led 3, lit when pump P3 is power supplied
F3
Fuse F3
4
Led 4, lit when pump P4 is power supplied
F4
Fuse F4
5
Terminal block
Fuse
FU1
FU2
FU3
FU4
FU5
Protection
PUMP 1
PUMP 2
PUMP 3
PUMP 4
Power card
Size
6,3 x 32
6,3 x 32
6,3 x 32
6,3 x 32
6,3 x 32
Rating
2,5 A
2,5 A
2,5 A
2,5 A
800 mA
Voltage
250 V
250 V
250 V
250 V
250 V