13 of 48
HRS Hevac Ltd AquaModule AMB
Installation, Operating & Instruction Manual
4.3 Wiring
details
4.3.1
Power terminal on PCB
1 2 3 4 5 6 7 8 9
10
11
12
13
14
15
N Ph
Ũ
N Ph
Ũ
N Ph
Ũ
N Ph
Ũ
N Ph
Ũ
230V Main
Pump 1
Pump 2
Pump 3
Pump 4
(Not used in UK)
Power supply
(Primary)
(Primary)
(Secondary)
Control box power supply: 230V 50Hz + Ground terminals 1,2 and 3.
Terminals 4 to 15 are dedicated to P1, P2, P3, (P4) 230V power supply.
Do not exceed 3A per pump.
4.3.2
230V 3 points actuator terminals on PCB
16
17
18
19
N Ph
+ -
230V 3 points actuator
Opening of the actuator is made sending 230V pulses between terminals 16 (N) and 18 (+).
Closing of the actuator is made sending 230V pulses between terminals 16 (N) and 19 (-).
Terminal 17 (permanent Phase) can be used with return to zero (RTZ) actuators.
3 points 230V and 0-10V signals (or pulses) are sent continuously even if they
are not wired.
4.3.3
Low voltage outputs on PCB
20
21
22
23
24
25
26
27
28
29
0V
S/S 0V
S/S
NO
C NC
24Vac AO1
(0-10V)
0V
Pump 1
Pump 2
Relay 1 contact
0-10V DC actuator, 24V AC 5VA power
Start / Stop
Start / Stop
NO or NC to
supplied
N/A N/A
choose
0V is common on both signals
4.3.4
Low voltage inputs (contacts / Sensors) on controller
31
33
35
36
37
40
41
42
46
47
GND
Bi1
Ipso Ipso
GND
UI1 UI2 UI3 Ipso
Ipso
P3
P4
S1
S2
S3
P1
P2
Remote Secondary
Temperature Primary
Common Contact* pump(s)
default Common sensor(s) pump(s)
default
input contact(s)*
input(s)*
input contact(s)*
*For each of these inputs / outputs, the second wire must be connected to the
common terminal 37 or 31 as per available space.
There is no polarity on all contacts and temperature sensors.
Temperature sensors’ inputs except S1 are already wired. To add a temperature
sensor, remove existing wire from the terminal and isolate its end. Connect the
sensor’s wire instead and its second wire to common terminal, 31 or 37.