CAUTION:
If installing a processor with a faster speed, update the system ROM before installing
the processor.
To download firmware and view installation instructions, see the
CAUTION: THE CONTACTS ARE VERY FRAGILE AND EASILY DAMAGED.
To avoid damage to
the socket or processor, do not touch the contacts.
CAUTION:
To prevent mechanical damage or depositing oil on your hands or other contamination,
hold the heatsink only by the edge of its base plate. Do not touch the heatsink fins.
Installing the processor heatsink assembly
Prerequisites
Before installing this option, ensure that you have the following:
• The components included with the hardware option kit
• T-30 Torx screwdriver
Procedure
1.
Identify the processor, heatsink, and socket module components
.
2.
.
3.
.
4.
5.
Remove all power:
a.
Disconnect each power cord from the power source.
b.
Disconnect each power cord from the server.
6.
Disconnect all peripheral cables from the server.
7.
Do one of the following:
•
Extend the server from the rack
•
Remove the server from the rack
.
8.
.
9.
.
10.
Install the processor heatsink assembly:
a.
Locate and align the Pin 1 indicator on the processor frame and the socket.
b.
Align the processor heatsink assembly with the heatsink alignment posts and gently lower it down
until it sits evenly on the socket.
The heatsink alignment posts are keyed. The processor will only install one way.
84
Hardware options installation
Summary of Contents for ProLiant DL180
Page 30: ...24 bay SFF hot plug drive model Fan bay numbering 30 Component identification...
Page 58: ...SFF 4 Install the drive LFF SFF 58 Hardware options installation...
Page 97: ...Secondary riser cage Slot 4 Slot 5 or 6 Hardware options installation 97...
Page 128: ...Box 2 to type a controller Box 2 to type p controller 128 Cabling...
Page 129: ...Box 3 to system board Box 3 to type a controller Cabling 129...
Page 130: ...Box 3 to type p controller 8 bay SFF power cable default 130 Cabling...
Page 135: ...Mini SAS cable to SAS expander Cabling 135...
Page 137: ...M 2 SSD enablement board installed in secondary riser Cabling 137...
Page 142: ...Cable routing Serial port Cable routing iLO Service Port SFF LFF 142 Cabling...
Page 144: ...Secondary riser cage Slot 4 Slot 5 or 6 144 Cabling...