Specification
Value
Operating
8 to 90% relative humidity (Rh), 24°C (75.2°F) maximum wet bulb
temperature, non-condensing.
Non-operating
5 to 95% relative humidity (Rh), 38.7°C (101.7°F) maximum wet bulb
temperature, non-condensing.
Power requirements
The following table lists the power requirements for the HP Proliant DL380 G9 server.
Table 1: HP 800 W CS power supply (92% efficiency)
Specification
Value
BTU
917 BTU/hr
Voltage
100V — 240V
Plug Type
NEMA — 15
Circuit Breaker
15 Amp
Pole
1
AMP Draw
2.7 @ 100VAC
Total Watts
269 W
Note:
These numbers are based on the following typical Avaya configuration:
• qty=2 – E5-2620v3 six core processors
• qty=8x4 GB – Memory (1Rx4 PC4-2133P –R Kit)
• qty=3 – 2.5” SFF SAS HDDs
• qty=1 – Ethernet 1Gb 2-port 332T adaptor
• qty=2 – 800W power supplies
Physical system protection requirements
To properly ventilate the system, you must provide a minimum clearance of:
• 63.5 cm (25 in) in front of the rack
• 76.2 cm (30 in) behind the rack
Power requirements
July 2016
Avaya CMS HPE DL20 G9 and DL380 G9 HIMT