38.7º C (101.7º F)
Non-operating
Relative humidity (noncondensing)
2
20% to 80%
Operating
5% to 95%
Non-operating
1
All temperature ratings shown are for sea level. An altitude derating of 1° C per 304.8 m (1.8° F per 1000
ft) to 3048 m (10,000 ft) is applicable. No direct sunlight allowed. Upper operating limit is 3,048 m (10,000
ft) or 70 Kpa/10.1 psia. Upper non-operating limit is 9,144 m (30,000 ft) or 30.3 KPa/4.4 psia.
2
Storage maximum humidity of 95% is based on a maximum temperature of 45° C (113° F). Altitude
maximum for storage corresponds to a pressure minimum of 70 KPa.
For more information on the c-Class enclosures, go to
http://www.hpe.com/servers/
bladesystem/enclosures
.
For more site preparation information, go to
http://www.hpe.com/info/Blades-docs
,
select
HPE Integrity BL860c i2 Server Blade
or
HPE Integrity BL860c i4 Server
Blade
in the list of servers, and then select the
Generalized Site Preparation
Guidelines
.
Sample Site Inspection Checklist
Table 3 Customer and Hewlett Packard Enterprise Information
Customer Information
Phone number:
Name:
City or Town:
Street address:
Country
State or province:
Zip or postal code:
Phone number:
Primary customer contact:
Phone number:
Secondary customer contact:
Phone number:
Traffic coordinator:
Hewlett Packard Enterprise information
Order number:
Sales representative
Date:
Representative making survey
Scheduled delivery date
Table 4 Site Inspection Checklist
Comment or
Date
Check either Yes or No. If No, include comment number or date.
Computer Room
No
Yes
Area or condition
Number
Is there a completed floor plan?
1.
Is adequate space available for maintenance needs? Front
36 inches (91.4 cm) minimum and rear 36 inches (91.4
cm) minimum are recommended clearances.
2.
Is access to the site or computer room restricted?
3.
8