5 Adjusting the system setpoint pressure
Precondition Access level 2 is activated.
The display shows the operating mode.
1. Press «Enter».
The main menu is displayed.
2. Select the
< Configuration ➙ Pressure control ➙ Pressure settings > menu.
The
pA switching value is displayed in the active line.
6 . 1 b a r 0 8 : 1 5 8 0 . 0 ° C
5.2.2 Pressure settings
Current menu
Setpoint pressure
Parameter to be adjusted
pA SP : 8.0 bar ¦ SD : -0.5 bar
Active line, setting for switching point pA
pB SP : 7.7 bar ¦ SD : - 0.5 bar
Setting for switching point pB
·········
System pressure low ☐
↓< 5.0 bar ¦ SD : 0.5 bar
3. Press «Enter» to switch into setting mode.
The current value flashes.
4. Use «UP» or «DOWN» to adjust the setting for the switching point
pA .
5. Press «Enter» to accept the setting.
6. Press the «Right» key once.
7. Press «Enter» to switch into the setting mode for the switching differential.
The current value flashes.
8. Use «UP» or «DOWN» to adjust the setting for the switching differential.
9. Press «Enter» to accept the setting.
10. If necessary, adjust the value for switching point pB in the same way.
11. Press «Escape» repeatedly to return to the main menu.
Further information See chapter 7.4 for the adjustment of the machine's pressure parameters.