Selecting the Location
WARNING:
The TK is designed for outdoor use only
.
HEARTH PRODUCTS CONTROLS CO
. must be
notified of any other use.
WARNING:
The TK creates very high temperatures-it is very important that combustibles and people are
kept at safe distances.
WARNING:
For installation of the 24vac powered TK, it is required to install a wall switch or breaker for
the TK electrical outlet away from the TK to prevent unwanted ignition of the fire pit.
WARNING:
The TK location must accommodate a gas shut off in an accessible area.
•
The gas line should be a minimum of 1/2” or larger based on the number of TK’s or other fire
features and the distance from the energy source to the TK. Consult your local professional for
proper gas line sizing.
•
To enjoy your TK, select a location that allows for sufficient clearance from combustible
materials.
•
Choose a location that allows easy access for installation and maintenance of the TK. Make sure
that trees and shrubbery are well clear around and above the TK.
•
Pick a location that allows sufficient horizontal room to enjoy the TK while allowing a safe
distance from the heat and flame.
•
The TK is designed to be installed on a post. It is recommended that the TK flame is a minimum
of 84” off the ground. This is a guideline. Installers should follow local code.
•
The unit needs to be installed in a manner that ensures that pedestrian traffic cannot get closer than
a 48” perimeter around the flame.
•
Select a location where the TK can be attended during operation. Never leave an operating TK
unattended or by someone not familiar with its operation or emergency shut off locations.
•
Wooden or solid surfaces such as granite or marble must be located far enough away that they do
not reach a temperature of more than 100 degrees F plus ambient air temperature.
Example: If surrounding air temperature is 70, the wood surface temperature must stay at
or below 170 degrees F.
•
TK Clearance:
TK Clearances
Sides Surrounding TK 48”
Above TK 96”
3)
Site Preparation
WARNING:
Ensure sufficient clearance from all combustibles and pedestrian traffic as outlined in
“Selecting The Location”.
WARNING:
Class II, 24VAC, 4 amps (14 gauge wire) must be supplied to the TK head and able to be
switched on and off from a remote location to allows for easy access or emergency.
POWER MUST
BE TURNED OFF WHEN NOT IN USE.
IMPORTANT: Design site so the gas connection and 24vac electric supply are accessible after installation
for maintenance.
IMPORTANT: If flex hose is used care must be taken not to drop the hose down the post. This can be
especially problematic if the post is buried in concrete.
IMPORTANT: It is not recommended to mortar the post in place. This may make servicing the unit
difficult. If the post will be mortared in place it may be advantageous to run solid pipe through the post to
prevent accidentally dropping the flex hose down the post.
IMPORTANT: Determine installation method from Figure 1 or plan another method following the
guidelines of this manual.