Appendix B
System Specifications
Electrical Specifications
95
Electrical Specifications
This section provides electrical specifications for hp rp7405/rp7410 servers.
Grounding
The site building shall provide a safety ground/protective earth for each AC service entrance to all cabinets.
Install a PE (protective earthing) conductor that is identical in size, insulation material, and thickness to the
branch-circuit supply conductors. The PE conductor must be green with yellow stripes. The earthing
conductor described is to be connected from the unit to the building installation earth or, if supplied by a
separately derived system, at the supply transformer or motor-generator set grounding point.
Circuit Breaker
The Marked Electrical for the hp rp7405/rp7410 server is 12 amps. The recommended circuit breaker size is
20 amps for North America. For countries outside North America, consult your local electrical authority
having jurisdiction for the recommended circuit breaker size.
System AC Power Specifications
Power Cords
The supplied power cord length is 15 feet (457.4 cm). Table B-3 lists the various power cables available for use
with a hp rp7405/rp7410 system. Each power cord is 15 feet (4.5 meters) in length with a IEC 60320-1 C19
female connector attached to one end.
Table B-3
Power Cords
Part Number
Description
Where Used
8120-6895
Stripped end, 240 volt
International-Europe
8120-6897
Male IEC309, 240 volt
International
8121-0070
Male GB-1002, 240 volts
China
8120-6899
Male CEEE 7/7, 240 volt
Continental Europe
8121-0558
Male ISI-32, 240 volts
Israel
8120-6903
Male NEMA L6-20, 240 volt
North America/Japan
Summary of Contents for rp7405
Page 6: ...Contents vi ...
Page 8: ...Tables viii ...
Page 11: ...Preface ...
Page 15: ...xi Figure 1 Declaration of Conformity ...
Page 22: ...xviii ...
Page 39: ...Chapter 2 17 2 Installation ...
Page 70: ...Chapter 2 Installation Booting HP UX using Boot Console Handler BCH 48 ...
Page 71: ...Chapter 3 49 3 Troubleshooting ...
Page 78: ...Chapter 3 Troubleshooting Common Installation Problems 56 ...
Page 79: ...Chapter 4 57 4 Removal and Replacement ...
Page 111: ...Appendix A 89 A Replaceable Parts ...
Page 122: ...Appendix B System Specifications Environmental Specifications 100 ...
Page 123: ...Appendix C 101 C Site Preparation ...