UPS operations 33
Main menu
Submenu
Display information or menu function
—
Battery status
Battery Charging/Floating/Resting, Charge
Level, ERM Number, and Runtime
Event Log
—
Displays events and alarms
Measurements
Output
Output watts and VA
—
Output
Output amps and power factor
—
Output
Output voltage and frequency
—
Input
Input voltage and frequency
—
Battery
Battery voltage and percent charge
Control
Go to Bypass mode
Transfers the UPS system to internal Bypass
mode
When this command is active, the option
changes to Go to Normal mode.
—
Battery Test
Schedules a battery test
—
Reset error state
Reset alarms
—
Load segments
Turns load segments on or off
—
Restore factory settings
Resets the UPS back to factory settings
Settings
Change language
Changes language settings. The default is
English.
—
User Password
Enables or disables password. Default: Disable.
If Enable is selected, the password is USER. The
password cannot be changed.
—
Set date and time
Sets date and time
—
Control commands from serial
port
Enables or disables serial port control
commands. Default: Enabled
—
Output voltage
Sets output voltage
—
Auto start delay
Selects load segment and delay time in seconds
—
Automatic on battery shutdown Selects load segment and delay time in seconds
—
On battery notice delay
Sets delay time in seconds
—
Site wiring fault alarm
Enables or disables site wiring fault alarm. The
default is Disabled
—
Battery low alarm
Sets battery low alarm. Default: 3 minutes.
—
Automatic battery test
Enables or disables battery test. Default:
Disabled
—
LCD contrast
Change LCD contrast. Default: +0
Identification
—
UPS Type / Part Number / Serial Number /
NMC Firmware / Comm Firmware / UPS
Firmware
Verifying the REPO port connection
NOTE:
While testing, operate connected equipment in a safe test mode so the effects do not
disrupt critical operations.
After connecting the REPO port (on page
21
):