Troubleshooting 44
If the Battery Charge LED is also red:
a.
Save your work, and power down the UPS ("
Powering down the UPS
" on page
36
).
b.
After the blackout or brownout is over, power up the UPS ("
Powering up the UPS
" on page
27
).
c.
Allow the UPS batteries to charge for 24 hours.
If the Battery Charge LED is also yellow or green:
a.
Consider saving your work and powering down the UPS (on page
36
). If the blackout or
brownout is prolonged, the Battery Charge LED turns red as the UPS batteries near depletion.
b.
After the blackout or brownout is over, power up the UPS ("
Powering up the UPS
" on page
27
).
c.
Allow the UPS batteries to charge for 24 hours.
Voltage Configuration LED is green
Action:
The UPS is automatically correcting high or low AC voltage on the utility line. No action is
required.
Output Load Level LED is red or flashing red
Action:
1.
Remove one or more load devices to reduce the power requirements.
2.
Initiate a self-test ("
Initiating a self-test
" on page
35
).
3.
If the condition persists, verify that the load devices are not defective.
Battery Charge LED is red
Action:
If the Power LED is flashing green:
a.
Save your work, and power down the UPS ("
Powering down the UPS
" on page
36
).
b.
After the blackout or brownout is over, power up the UPS ("
Powering up the UPS
" on page
27
).
c.
Allow the UPS batteries to charge for 24 hours.
If the Power LED is green:
a.
Continue to let the batteries charge until the Battery Charge LED is green.
b.
Initiate a self-test ("
Initiating a self-test
" on page
35
).
Summary of Contents for R2200 INTL
Page 1: ...HP R T2200 UPS User Guide October 2006 Third Edition Part Number 404314 003 ...
Page 17: ...Installation 17 ...
Page 28: ...Installation 28 1 Attach the logo badge above the LED Control panel ...
Page 30: ...Installation 30 ...
Page 51: ...Warranty information 51 Notification from power management software ...