Specifications 102
Cord model number
Description
Input plug type
Length
12kVA Parallel NA
12 kW UL parallel
Anderson
0.5 m (1.5 ft)
12kVA INTL
12 kW CE input
IEC 309-32 A
3.7 m (12 ft)
8kVA INTL
12 kW CE input/output IEC 309-16 A
3.7/1.2 m (12/4 ft)
12kVA Parallel INTL
12 kW CE parallel
Anderson
0.5 m (1.5 ft)
Power Bus Bar and Wireway specifications
Power Bus Bar
Wireway
Dimensions (WxDxH) 14.0 x 11.3 x 182.7 cm (5.5 x 4.4 x 71.9 in)
Weight
19 kg (42 lb)
20 kg (45 lb)
UPS connections
6 power connections available
Rack placement
Installed to the rack rear vertical rail
(pre-installed)
Fits into the bottom 6U of standard
rack space (pre-installed)
HP 10642 G2 Rack specifications
U height
Width
Depth
Weight (without
side panels)
Dynamic load (gross)
Static load
42U
600 mm
(23.8 in)
1,000 mm
(39.4 in)
115 kg (253 lb)
907.2 kg (2,000 lb)
907.2 kg (2,000
lb)
UPS input specifications
3 Phase UPS NA
3 Phase UPS INTL
Nominal voltage
120/208 V three-phase
230/400 V three-phase
Nominal frequency
50/60 Hz
50/60 Hz
Frequency range
45-65 Hz
45-65 Hz
Default frequency
Auto-detected
Auto-detected
Rated input current—12kVA
models
36 A
24 A
Rated input current—8kVA
models
24 A
16 A
Connections—12kVA models IEC 309-60 A power cord
IEC 309-32 A power cord
Connections—8kVA models L21-30P power cord
IEC 309-16 A power cord
Connections—Parallel models Single Anderson input/output cord
connects to the Power Bus Bar
Single Anderson input/output cord
connects to the Power Bus Bar
Noise filtering
MOVs and common mode line filter MOVs and common mode line filter
Input power factor
High efficiency setting: load
dependent
High efficiency setting: load dependent
Standard setting: >0.99
Standard setting: >0.99
Input mode
Three-phase
Three-phase