HPE Smart Storage Administrator
HPE Smart Storage Administrator
HPE SSA is the main tool for configuring arrays on HPE Smart Array SR controllers. It exists in three interface formats: the HPE SSA GUI,
the HPE SSA CLI, and HPE SSA Scripting. All formats provide support for configuration tasks. Some of the advanced tasks are available
in only one format.
The diagnostic features in HPE SSA are also available in the standalone software HPE Smart Storage Administrator Diagnostics Utility
CLI.
During the initial provisioning of the server or compute module, an array is required to be configured before the operating system can be
installed. You can configure the array using SSA.
HPE SSA is accessible both offline (either through HPE Intelligent Provisioning or as a standalone bootable ISO image) and online:
Accessing HPE SSA in the offline environment
IMPORTANT:
IMPORTANT: If you are updating an existing server in an offline environment, obtain the latest version of HPE SSA
through Service Pack for ProLiant before performing configuration procedures.
Using one of multiple methods, you can run HPE SSA before launching the host operating system. In offline mode, users can configure
or maintain detected and supported devices, such as optional Smart Array controllers and integrated Smart Array controllers. Some
HPE SSA features are only available in the offline environment, such as setting the boot controller and boot volume.
Accessing HPE SSA in the online environment
This method requires an administrator to download the HPE SSA executables and install them. You can run HPE SSA online after
launching the host operating system.
For more information, see HPE SSA online help.
HPE Smart Storage Administrator
165
Summary of Contents for ProLiant DL345 Gen10 Plus
Page 47: ...Customer self repair 47 ...
Page 48: ...Customer self repair 48 ...
Page 49: ...Customer self repair 49 ...
Page 50: ...Customer self repair 50 ...
Page 68: ...Removing a riser cage 68 ...
Page 76: ...Removing and replacing the cable management arm 76 ...
Page 77: ...Removing and replacing a power supply Removing and replacing a power supply 77 ...
Page 135: ...System battery replacement System battery replacement 135 ...
Page 139: ...Removing and replacing the system board Removing and replacing the system board 139 ...
Page 149: ...Troubleshooting NMI functionality Troubleshooting resources Troubleshooting 149 ...
Page 152: ...Diagnostic tools Diagnostic tools 152 ...
Page 188: ...HPE Basic Drive LED definitions 188 ...
Page 193: ...Fan bay numbering The arrow points to the front of the server Fan bay numbering 193 ...
Page 197: ...Storage cabling Storage cabling 197 ...
Page 198: ...Drive power cabling Drive power cabling 198 ...
Page 201: ...2 SFF drive power cabling 2 SFF drive power cabling 201 ...
Page 202: ...Storage controller cabling Storage controller cabling 202 ...
Page 232: ...Energy pack cabling Energy pack cabling 232 ...
Page 234: ...Storage controller backup power cabling 234 ...
Page 235: ...M 2 SATA SSD cabling M 2 SATA SSD cabling 235 ...
Page 237: ...Fan cabling Fan cabling 237 ...
Page 238: ...OCP bandwidth upgrade cabling OCP bandwidth upgrade cabling 238 ...
Page 239: ...Serial port cabling Serial port cabling 239 ...
Page 240: ...Chassis intrusion detection switch cabling Chassis intrusion detection switch cabling 240 ...