
Input Requirements
Input Requirements
Input Requirements
Input Requirements
Reference the Site Preparation Guide for detailed power configuration requirements.
Requirements
Requirements
Requirements
Requirements
Value
Value
Value
Value
Conditions/Comments
Conditions/Comments
Conditions/Comments
Conditions/Comments
Nominal Input Voltage (VAC rms)
200/208/220/230/240
Input Voltage Range (VAC rms)
200-240
Auto selecting. Measure at input terminals.
Frequency Range (Hz)
50/60
Number of Phases
3
3-phase 5-wire with power cord;
3-phase 4-wire with power cord
Maximum Input Current (A rms), 3-Phase
5-wire
20
3-phase source with a source voltage of
220 VAC measured phase to neutral
Maximum Input Current (A rms), 3-Phase
4-wire
40
3-phase source with a source voltage of
either 208 VAC or 230 VAC measured
phase-to-phase
Maximum Inrush Current (A peak)
90
Circuit Breaker Rating (A), 3-Phase 5-wire
25 A
Per phase
Circuit Breaker Rating (A), 3-Phase 4-wire
45 A
Per phase
Power Factor Correction
0.95 minimum
Ground Leakage Current (mA)
>3.5 mA, with 6 BPSs installed
Warning label applied to the PDCA at the
AC Mains input
Cooling Requirements
Cooling Requirements
Cooling Requirements
Cooling Requirements
The cooling system in Superdome was designed to maintain reliable operation of the system in the
specified environment as shown in the Superdome Specifications Table
Superdome Specifications Table
Superdome Specifications Table
Superdome Specifications Table. In addition, the system is
designed to provide a redundant cooling (i.e. N+1 fans and blowers) that allows all of the
cooling components to be "hot swapped." The typical power dissipation for the PA-8600 is
28,850 BTUs/hour for a fully populated 32-processor cabinet. For PA 8700, the typical power
dissipation is approximately 23,660 BTUs/hour for a fully populated 32-processor cabinet.
NOTE:
NOTE:
NOTE:
NOTE: For other configurations see "Site Prep Guide 6th Edition", Table 5. For maximum power
dissipation, see Superdome Specifications Table
Superdome Specifications Table
Superdome Specifications Table
Superdome Specifications Table under Site Preparation.
Superdome was designed to operate in all data center environments with any traditional room
cooling scheme (i.e. raised floor environments) but in some cases where data centers have
previously installed high power density systems, alternative cooling solutions may need to be
explored by the customer. Since no such system has been available previously, HP teamed with
Liebert to develop an innovative data room cooling solution called DataCool. DataCool is a
patented overhead climate system utilizing fluid based cooling coils and localized blowers capable
of cooling heat loads of several hundred watts per square foot. Some of DataCool's highlights are
listed below:
Liebert has filed for several patents on DataCool
DataCool, based on Liebert's TeleCool, is an innovative approach to data room cooling
Liquid cooling heat exchangers provide distributed cooling at the point of use
Delivers even cooling throughout the data center preventing hot spots
Capable of high heat removal rates (500 W per square foot)
Floor space occupied by traditional cooling systems becomes available for revenue generating
equipment.
Enables cooling upgrades when installed in data rooms equipped with raised floor cooling
DataCool is a custom-engineered overhead solution for both new data center construction and for data
QuickSpecs
HP 9000 Superdome Servers (PA-8600, PA-8700, PA-
HP 9000 Superdome Servers (PA-8600, PA-8700, PA-
HP 9000 Superdome Servers (PA-8600, PA-8700, PA-
HP 9000 Superdome Servers (PA-8600, PA-8700, PA-
8800 and PA-8900)
8800 and PA-8900)
8800 and PA-8900)
8800 and PA-8900)
System Management Features
DA - 11721 Worldwide — Version 28 — October 23, 2009
Page 32