change the grid underfrequency protection limit via Hoymiles monitoring 

system with the consent of the local power operator.

 

146 

Rapid grid frequency 

change rate

 

1. If the alarm occurs accidentally, the grid frequency may be abnormal 

temporarily.  The  microinverter  can  recover  automatically  after  grid 

frequency becomes normal. 

2.  If  the  alarm  occurs  frequently,  check  whether  the  grid  frequency 

change rate is within the acceptable range. If no, contact the local power 

operator  or  change  the  grid  frequency  change  rate  limit  via  Hoymiles 

monitoring system with the consent of the local power operator.

 

147 

Power grid outage

 

Please check whether there is a power grid outage.

 

148 

Grid disconnection

 

Please check whether the AC switch or AC wiring is normal.

 

149 

Island detected

 

1.  If  the  alarm  occurs  accidentally,  the  grid  voltage  may  be  abnormal 

temporarily.  The  microinverter  can  recover  automatically  after  grid 

voltage becomes normal. 

2. If the alarms occur frequently on all the microinverters in your station, 

contact the local power operator to check whether there is a grid island. 

3.If  the  alarm  still  exists,  contact  your  dealer  or  Hoymiles  technical 

support.

 

205 

Input port1 

overvoltage 

1.Please make sure that the PV module open-circuit voltage is less than 

or equal to the maximum input voltage. 

2.  If  the  PV  module  open-circuit  voltage  is  within  the  normal  range, 

contact your dealer or Hoymiles technical support.

 

206 

Input port2 

overvoltage 

1.Please make sure that the PV module open-circuit voltage is less than 

or equal to the maximum input voltage. 

2.  If  the  PV  module  open-circuit  voltage  is  within  the  normal  range, 

contact your dealer or Hoymiles technical support.

 

207 

Input port1 

undervoltage

 

1.Please make sure that the PV module open-circuit voltage is less than 

or equal to the maximum input voltage. 

2.  If  the  PV  module  open-circuit  voltage  is  within  the  normal  range, 

contact your dealer or Hoymiles technical support.

 

208 

Input port2 

undervoltage

 

1.Please make sure that the PV module open-circuit voltage is less than 

or equal to the maximum input voltage. 

2.  If  the  PV  module  open-circuit  voltage  is  within  the  normal  range, 

contact your dealer or Hoymiles technical support.

 

209 

Port1 No input

 

1. Please confirm whether this port is connected to the PV module; 

2. If the PV module is connected, please check the DC cable connection 

between this port and the PV module.

 

210 

Port2 No input

 

1. Please confirm whether this port is connected to the PV module; 

2. If the PV module is connected, please check the DC cable connection 

between this port and the PV module.

 

301 

Hardware Error Code 

301

 

1.  If  the  alarm  occurs  accidentally  and  the  microinverter  can  still  work 

normally, no special treatment is required. 

2. If the alarm occurs frequently and cannot be recovered, contact your 

dealer or Hoymiles technical support.

 

Summary of Contents for HM-500T

Page 1: ...Version 1 0 April 2020...

Page 2: ...control the production of a single photovoltaic module directly consequently improving the flexibility and reliability of the system About the Manual This manual contains important instructions for t...

Page 3: ...nals Introduction 8 3 4 Dimension mm 8 4 About Function 9 4 1 Work Mode 9 5 About Installation 9 5 1 Accessories 9 5 2 Installation Precaution 9 5 3 Space Distance Required 10 5 4 Preparation 10 5 5 P...

Page 4: ...ification 22 8 2 Power Quality Response Modes 22 8 3 DRM 23 9 Technical Data 23 9 1 DC Input 24 9 2 AC Output 24 9 3 Efficiency Safety and Protection 24 9 4 Mechanical Data 24 9 5 Features 25 Appendix...

Page 5: ...ls Used The safety symbols in this user manual are show as below 2 About Safety 2 1 Important Safety Instructions The HM 500T HM 600T HM 700T HM 800T Microinverter is designed and tested according to...

Page 6: ...sconnect switches and Over current Protection Devices OCPD Only one photo voltaic module can be connected to one input of the inverter Do not connect batteries or other sources of power supply The inv...

Page 7: ...e limits for CE EMC which can provide reasonable protection against harmful energy However if not installed according to the instructions the microinverter may cause harmful interference to radio equi...

Page 8: ...6 50 peak efficiency 96 70 in 2015 3 2 Highlights Maximum output power up to 500W 600W 700W 800W Adapted to 60 72 cells PV panels Peak efficiency 96 70 CEC weighted efficiency 96 50 Static MPPT effici...

Page 9: ...current condition is contradicted with Microinverter operating requirement No house loads or the Export control value has been set as 0 on the DTU under the Zero Export Control mode 5 About Installati...

Page 10: ...f for better communication with Hoymiles DTU Please contact with Hoymiles technical engineer if there is any special circumstance 5 4 Preparation Installation of the equipment is carried out based on...

Page 11: ...orrect operation of electronic equipment When choosing the position of installation comply with the following conditions Install only on structures specifically conceived for photovoltaic modules supp...

Page 12: ...ation Steps Step 1 Fix Microinverter on the Rail A Mark the approximate center of each panel on the frame B Fix the screw on the rail C Hang the microinverter on the screw shown as picture below and t...

Page 13: ...AC connector unlock tool and insert the tool into the side of AC port Step 3 Install AC End Cable A Prepare the AC end cable with the proper length and insert one side of the cable into the cap Match...

Page 14: ...HM 500T HM 600T HM 700T HM 800T B Affix the serial number label to the respective location on the installation map Step 5 Connect PV Modules A Mount the PV modules above the microinverter B Connect t...

Page 15: ...dissipation 3 If both the ventilation and ambient temperature meet the requirements contact your dealer or Hoymiles technical support 125 Grid configuration parameter error 1 Check if the grid config...

Page 16: ...2 If the alarm occurs frequently check whether the grid voltage is within the acceptable range If no contact the local power operator or change the grid overvoltage protection limit via Hoymiles moni...

Page 17: ...or equal to the maximum input voltage 2 If the PV module open circuit voltage is within the normal range contact your dealer or Hoymiles technical support 206 Input port2 overvoltage 1 Please make sur...

Page 18: ...occurs accidentally and the microinverter can still work normally no special treatment is required 2 If the alarm occurs frequently and cannot be recovered contact your dealer or Hoymiles technical s...

Page 19: ...roinverter follow the steps in the order shown 1 Verify the utility voltage and frequency are within ranges shown in the in appendix Technical Data of this microinverter 2 Check the connection to the...

Page 20: ...d insulation the Microinverters are not designed to allow internal repairs The AC output wiring harness AC drop cable on the Microinverter cannot be replaced If the cord is damaged the equipment shoul...

Page 21: ...eps to install the replacement unit Go to the monitoring platform if customer already register this station online please access the Device List page and find the device that you just replaced Please...

Page 22: ...long periods check that it is correctly packed The equipment must be stored in well ventilated indoor areas that do not have characteristics that might damage the components of the equipment Take a co...

Page 23: ...lowing before installing Hoymiles Microinverter System Verify that the voltage and current specifications of the PV module must match those of the microinverter The maximum open circuit voltage rating...

Page 24: ...800T Rated output apparent power VA 500 600 700 800 Rated output current A 2 17 230V 2 08 240V 2 61 230V 2 50 240V 3 04 230V 2 92 240V 3 48 230V 3 33 240V Nominal output voltage range V 230 180 275 24...

Page 25: ...70 28 250 170 28 250 170 28 Weight kg 2 6 2 6 2 6 2 6 Enclosure rating Outdoor NEMA IP67 Cooling Natural convection No fans Model HM 500T HM 600T HM 700T HM 800T Communication 2 4GHz Proprietary RF No...

Page 26: ...2019 Hoymiles Converter Technology Co Ltd All rights reserved 26 HM 500T HM 600T HM 700T HM 800T Appendix 1 Installation Map...

Page 27: ...ix 2 WIRING DIAGRAM 230VAC SINGLE PHASE UP TO 6 HM 800s PER AC BRANCH CIRCUIT GROUND NEUTRAL W AC DISTRIBUTION PANEL OR SUBPANEL METER AC BRANCH CABLE BROWN L BLUE N YELLOW GREEN G BRANCH END CAP L1 P...

Page 28: ...0s PER AC BRANCH CIRCUIT UP TO 6 HM 800s PER AC BRANCH CIRCUIT UP TO 6 HM 800s PER AC BRANCH CIRCUIT GROUND NEUTRAL W AC DISTRIBUTION PANEL OR SUBPANEL METER AC BRANCH CABLE BROWN L BLUE N YELLOW GREE...

Reviews: