14 TroubleShooting
Chart
48
PROBLEM
PROBABLE CAUSE
REMEDY
Head pressure controls defective.
Replace defective head
pressure control.
(Headmaster Control)
Condensing unit undersized.
Replace unit with
properly sized condensing
unit.
Ice flakes too small and
too "powdery"
Evaporating temp. too low because
condensing unit is oversized.
Install EPR and adjust
evaporating temperature
between -5°F and -10°F.
(-30°F to -35° F for
seawater)
) Dull carbon steel ice blade.
Replace ice blade with
stainless steel blade.
Operation with excessive
"chatter" may result in
damage to speed reducer,
motor, coupling and main
bearings.
X Ice flaker "chatters"
excessively, does not run
smoothly.
Excessive ice blade clearance.
Inspect and adjust ice
blade clearances. (see
section 11, service &
adjustment).
Worn main bearings and/or shaft.
Replace bearings and/or
shaft (if worn) (see section
11, service & adjustment).
Too much ice accumulation
in bottom water collecting
trough.
Ice deflector not properly
positioned.
Reposition ice deflector.
(see section 11, service &
adjustment)
Ambient temperature too cold.
Install cartridge heaters in
ribs, ** flaker must be
ambient temperatures
above 40°F.
Too much ice accumulation
in bottom water collecting
trough and in water
sump, and excessive ice
build up on bottom 3
"ribs"
Water temperature too cold.
Water temperature must
be above 40°F. Install
water mixing valve to
supply 60°F (ideally)
water to ice flaker.
Ice in storage bin too wet.
(Water dripping into bin
with ice).
Water level in sump set too high
(water overflows bottom
collecting trough)
Adjust water float valve to
maintain water level
3
"
below water return trough
Summary of Contents for Rapid Freeze
Page 6: ......
Page 16: ...6 SEAWATER MODEL INSTALLATION 10 ASSEMBLY DRAWING 11ESS 21ESS...
Page 17: ...6 SEAWATER MODEL INSTALLATION 11 ASSEMBLY DRAWING 31ES 31ESS...
Page 18: ...6 SEAWATER MODEL INSTALLATION 12 ASSEMBLY DRAWING 51ES 51ESS...
Page 19: ...6 SEAWATER MODEL INSTALLATION 13 ASSEMBLY DRAWING 11EFS 21EFS...
Page 20: ...6 SEAWATER MODEL INSTALLATION 14 ASSEMBLY DRAWING 51EFS...
Page 21: ...6 SEAWATER MODEL INSTALLATION 15 ASSEMBLY DRAWING 10ESS 20ESS...
Page 22: ...6 SEAWATER MODEL INSTALLATION 16 ASSEMBLY DRAWING 30ES 30ESS...
Page 23: ...6 SEAWATER MODEL INSTALLATION 17 ASSEMBLY DRAWING 50ES 50ESS...
Page 28: ...9 How The Rapid Freeze Flaker Operates 22 ICE FLAKER CUTAWAY DRAWING EXHIBIT 26...
Page 38: ...12 Control Panel Wiring Diagrams 32 Control Panel Schematic E20T40 RL...
Page 39: ...12 Control Panel Wiring Diagrams 33 460 3 60 WIRING E20T47...
Page 42: ...12 Control Panel Wiring Diagrams 36 220 1 50 Control Panel Schematic E20T40 RL 50...
Page 43: ...12 Control Panel Wiring Diagrams 37 380 3 50 Control Panel Schematic E20T60...
Page 64: ...15 Service Adjustment 58 EXHIBIT 40...