3.3 Guarantee
With the acquisition of a Hoval unit, you also obtain
comprehensive warranty cover under the Hoval terms
of warranty. This warranty is, however, dependent on ob-
servance of the operating instructions and on complian-
ce with the applicable legal regulations. Non-compliance
with the above will invalidate all liability and warranty
claims against Hoval.
4
Technical information
4.1 Description
Bathroom
Bedroom
Technology
room
HomeVent
®
Living room
Kitchen
Supply air
Fresh air
Extract air
Exhaust air
Extract air
Fresh air
Supply air
Exhaust air
Energy recovery
The built-in enthalpy recovery unit withdraws energy
from the extract air and transfers it to the supply air.
This enables the intelligent (temperature) and the latent
(humidity) energy to be transferred. The transmission
performance is regulated between 0 and 100%
depending on the outdoor temperature.
IMPORTANT INFORMATION AND TECHNICAL INFORMATION
The advantages of the enthalpy recovery unit are:
•
Temperature efficiency up to 90%
•
Degree of humidity recovery up to 95%
• Transmission performance can be adjusted
continuously
• No preheating required (down to -20°C)
• No condensation
• No bypass required
Air filtration
The fresh air goes through two cleaning stages,
ensuring the highest standard. A fine-meshed prefilter
(washable) at the entry of the unit prevents insects, lea-
ves, etc. from reaching the unit. Before the fresh air lea-
ves the unit, it flows through a high-capacity fine pollen
filter (F7). In addition, an activated carbon filter can be
installed on the supply air side (optional). The operator
receives a message when it is time to change the filter.
Air delievery
Two backward-curved centrifugal fans with EC direct
current motors deliver the air. The rotating wheel made
of high-tech composite material is produced in one
piece with optimised fluid mechanics, and ensures quiet
operation of the unit. The electronics built into the motor
enable the air volumes to be finely regulated.
Suitability for winter
Due to the built-in enthalpy recovery unit, no condensate
is formed in the unit. Ice formation is not possible. No
preheating (electric air heater) is necessary for outdoor
temperatures down to -20 °C. The air volume ratio
between the supply air and extract air is not changed.
Summer operation
The energy recovery is reduced to a minimum according
to the outdoor temperature. This enables night cooling
(free cooling) in the summer as well as when the sea-
sons change. It is not necessary to arrange for a bypass
via dampers and a drive. In addition, the CoolVent opti-
on can actively recover cold in
air-conditioned buildings. The hot fresh air is cooled and
if necessary dried with the air-conditioned extract air.
Installation
The HomeVent
®
comfort ventilation unit is characterised
by a compact design. It is possible to access the unit
from both sides for servicing. No condensate forms in
the unit, meaning that it can be installed in any position
imaginable. We recommend the corresponding mounting
kits with solid-borne noise decoupling for the different
installation positions.
Standard operator terminal BG02 E
The operator terminal is suitable for on-wall mounting.
The target air volume and the maximum air humidity can
be set with two rotary knobs. With the party button, the
air volume can be increased for a limited period of time.
Connection to the HomeVent
®
comfort ventilation unit via
RJ45 plug connection. The unit can also be installed in a
secondary room.