Non-Programmable Single Stage Thermostat 

                                       

Reference  No.:

 

HTW-ST01-A 

 

                                                         

 

- 6 -

                                                                            Version 2019-1.0                                                                                             

▼ 

bL (2) 

1 – 3 

Select display backlight : 

(1) = OFF. 

(2) = 30 seconds on any 
button push. 

(3) = ON.   

Default = 2. 

Option (3) can be activated 
only if the common is used.

 

-Note 2

 

▼ 

FL (00) 

00, 1 thru12 

Select filter time in months.   

Default = 00. 

A selection of “00” deactivates the 

filter feature.

 -Note 3

 

▼ 

FC (F) 

F or C 

°F or °C display. Default = F 

▼ 

CL (0) 

+4 TO -4 

Select temperature calibration 
point up to 4° higher or 4°lower.   

Default = 0 

▼ 

CP (5) 

0 or 5 

Compressor Lockout delay.   

0 = none,        1= 1 Min     

2=2 Min            3=3 Min   

4=4 Min            5 = 5Min         

Default = 5 

-Note 4

 

Notes: 

1.

 

The FA setting is used to produce shorter Heating/Cooling cycles. The SL setting produces a longer Heating/Cooling cycle. 
Both settings produce very accurate temperature control and can be set to your personal preference. FA cycles the system 
at a 0.5ºF (0.5ºC) differential, and SL cycles the system at 1.5ºF (1.5ºC). 

 

2.

 

When operated from batteries only, the LCD display backlight will be illuminated less than 5 seconds after each button 
pressed, options (2) & (3) will operate the same when terminal “C” is not connected. 

 

3.

 

The thermostat will display the Filter Alarm after a set time of operation. This is a reminder to change or clean your air 
filter. This time can be set from 0 to 12 months in 1 month increments. Selection of 00 WILL CANCEL THIS FEATURE. 
When  Filter  Alarm  is  displayed,  you  can  clear  it  by  pressing  the 

  and 

  buttons.  This  resets  the  timer  and  starts 

counting the days until the next filter change. 

 

4.

 

Select  compressor  lockout  delay  0,1,2,3,4,5  To  protect  the  compressor  from  short  cycling,  you  can  select  compressor 
off-time cycle between 0 to 5 minutes. When the thermostat compressor time delay occurs, the Cool On or Heat On display 
will flash during compressor lockout. 

 

 

 Always turn off power at the main power source by removing the fuse, or switching the circuit breaker to the off position before installing, 

removing, cleaning, or servicing this thermostat. 

 Use this thermostat only as described in this manual. Read all of the information in this manual before installing this thermostat. 

 Use a professional

 

personnel / installer to install this thermostat. 

 This is a 24VAC low-voltage thermostat, do not install on voltages higher than 30 vac. 

 ALL wiring must conform to local and national building and electrical codes and ordinances. 

 Do not short (jumper) across terminals on the gas valve or at the system control to test installation.   

This will damage the thermostat and void the warranty. 

 Do not switch the system to cool if the temperature is below 50ºF (10ºC). This may damage the air conditioning system. 

 Replace batteries when the battery icon indicates the low battery message. 

 Change the Air Filter when the Filter Change Icon begins blinking.

 

Important Safety Information 

 

Summary of Contents for HTW-ST01-A

Page 1: ...nent user setting retention during power loss No batteries are required Apply to 24VAC or 2 AA alkaline batteries power supply Air Filter change Indicator Low Battery Indicator Temperature calibration 4 or 5 wire compatible C is optional for non heat pump systems Manual Changeover Fan Switch Easy operation friendly Mercury Free Environmentally Safe Built in compressor protection Power Supply 20VAC...

Page 2: ...your screwdriver carefully unscrew one wire at a time from the terminal block and attach the corresponding wire label sticker Please note that not all terminals may be used and that there s no standard color code for thermostat wires so your wire colors may vary For your reference we ve included a terminal label reference chart as below to help you connect the wires in your old thermostat to your ...

Page 3: ...t base from your wall Mounting and Wiring Your New Thermostat 1 Install new thermostat base 2 Connect wires to corresponding terminal blocks Match each labeled wire to it s corresponding terminal on the mounted thermostat base Insert each labeled wire into the hole of it s matching terminal and using the screwdriver tighten the screw on the terminal block securely 3 Set switch and advanced wiring ...

Page 4: ...position If the heating system has a standing pilot be sure to light it Press to adjust thermostat setting room temperature The heating system should begin to operate Press to adjust temperature setting below room temperature The heating system should stop operating Cooling system Move SYSTEM switch to COOL position Press to adjust thermostat setting below room temperature The blower should come o...

Page 5: ...ll show dEF blink Child Lock Quickly and simultaneously press the and three times to lock the temperature adjustment and again to unlock RESET function This function can help operator to recovery system when fault happened display out of order or system halted Please use a pin to insert in button RESET hole till sounded click then loosen it Move the SYSTEM switch to the OFF position then press and...

Page 6: ...increments Selection of 00 WILL CANCEL THIS FEATURE When Filter Alarm is displayed you can clear it by pressing the and buttons This resets the timer and starts counting the days until the next filter change 4 Select compressor lockout delay 0 1 2 3 4 5 To protect the compressor from short cycling you can select compressor off time cycle between 0 to 5 minutes When the thermostat compressor time d...

Reviews: