R8E V2 Superchiller Remote
230V / 50Hz
lancerbeverage.com
Page 9 of 27
Hoshizaki Lancer reserve the right to change specifications without notice.
Part No: 68000009
Images are for illustration purposes only as product may vary.
No 027 – 7 March 2013
6.4
Mounting Superchiller
Install on a flat, level surface using adjustable legs or casters (Optional).
Fix to supporting structure using 4 x ¾” BSW bolts screwed into base supports.
Caution
Superchiller operational weight is 327kg; ensure that all
supporting structures are certified for this loading by a
registered Mechanical Engineer.
Supporting structure must be securely fixed to floors or walls.
6.5
Connecting Superchiller to Remote Condensing Unit
The R8E Superchiller is supplied with a nitrogen holding charge only. It requires a connection to a
remote condensing unit with a minimum capacity of 3.2kW @ -5
C SST, 43
C ambient temperature.
Note
: the serial plaque on the R8E Superchiller must be checked to confirm correct refrigerant type
before connection to the condensing unit.
Suction and liquid line should be sized correctly to provide a minimum return vapour velocity of
7.5m/s (vertical risers) and 3.5m/s horizontal sections.
Suction line pressure drop should comply with industry standard guidelines of 1.1
K and must not
exceed 2
K.
Note:
An oil separator must be used on the remote condensing unit and P traps must be installed
every 3m vertical lift of suction line.
Standard refrigeration practice of deep evacuation (150 micron) before charging the system is
necessary. The electronic icebank control closes 2 x liquid line solenoid valves to start the pump
down cycle on condensing unit before turning off via the low pressure switch on the condensing unit.
6.6 Electrical
Connection
This unit requires a 10 amp power supply.
Check the name plate on the machine for electrical supply requirements. Use only the power
supply specified on the name plate.
Warning
If the supply cord is damaged, it must be replaced by the
manufacturer, its service agent or similarly qualified persons in order
to avoid a hazard.
Warning
To avoid possible fatal electric shock or serious injury the
Superchiller must be electrically grounded.
Electrical Connection Must Be Made In Accordance With The
Appropriate Local Codes And Regulations.
Use of an RCD is recommended.