12
E. Electrical Connection
WARNING
For All Models
• Electrical connection must be hard-wired and must meet national, state, and local
electrical code requirements. Failure to meet these code requirements could result
in death, electric shock, serious injury, fire, or damage.
• The icemaker requires an independent power supply of proper capacity. See
the nameplate for electrical specifications. Failure to use an independent power
supply of proper capacity can result in a tripped breaker, blown fuse, damage to
existing wiring, or component failure. This could lead to heat generation or fire.
•
THE ICEMAKER MUST BE GROUNDED.
Failure to properly ground the icemaker
could result in death or serious injury.
• Electrical connection must be made in accordance with the instructions on the
"WARNING" tag, provided with the pig tail leads in the junction box. See Fig. 4.
Additional Warnings for Remote Models
• To reduce the risk of electric shock, make all remote condenser unit connections
before connecting the icemaker power supply.
NOTICE
On remote models, the appliance must have power for a minimum of 4 hours prior
to startup to prevent compressor damage.
• Usually an electrical permit and services of a licensed electrician are required.
• The maximum allowable voltage variation is ±10 percent of the nameplate rating.
•
NOTICE!
KM-1100MAJ50 models, the main transformer’s voltage tap switch must be
positioned to match incoming voltage at startup.
• The opening for the power supply connection is 7/8" DIA to fit a 1/2" trade size conduit.
L
N
230V
4A1169-011
KM-1100MAJ50
WARNING
ELECTRICAL CONNECTION
THIS UNIT MUST BE GROUNDED
Failure to properly ground or wire
this unit could result in death,
serious injury, or severe damage
to the icemaker. The light blue lead
must be connected to the neutral
conductor of the power source.
See diagram below.
4A5033-010
220-240/50/1
JUNCTION BOX
BROWN
LIGHT
BLUE
L
N
220
-240V
Fig. 4