WARNINGS  

!

WARNING - If the equipment is used in a manner not specified by 
Horner APG, the protection provided by the equipment may be 
impaired.

WARNING - EXPLOSION HAZARD - Do not disconnect equipment 
unless power has been removed or the area is known to be non-
hazardous
AVERTISSEMENT - RISQUE D’EXPLOSION -Ne débranchez pas 
l’équipement tant que l’alimentation n’a pas été coupée ou que la 
zone n’est pas dangereuse.

WARNING - EXPLOSION HAZARD - Substitution of any component 
may impair suitability for Class I, Division 2
AVERTISSEMENT - RISQUE D’EXPLOSION -Le remplacement de tout 
composant peut nuire à la compatibilité avec la classe I, division 2

WARNING – POSSIBLE EQUIPMENT DAMAGE - Remove power from 
the I/O Base and any peripheral equipment connected to this local 
system before adding or replacing this or any module.
AVERTISSEMENT - DOMMAGES POSSIBLES À L’ÉQUIPEMENT - 
Coupez l’alimentation de la base d’E / S et de tout équipement 
périphérique connecté à ce système local avant d’ajouter ou de 
remplacer ce module ou tout autre module.

!

WARNING -  Outputs should be connected to the same voltage levels 

(all connect to 24V supply sources)

WARNING - Digital Outputs are non-isolated and considered 

hazardous live.

WARNING - Loads for outputs require a Class 2 or Limited Power 

Source from a UL Listed power supply.

SAFETY

a. All applicable codes and standards should be followed in the 
installation of this product.
b. Shielded, twisted-pair wiring should be used for best performance.
c. Shields should be grounded at one end only, preferably at the end 
providing the best noise shunting.

 SAFETY

 

PART NUMBER  

HE959CNX116                   

 

TECHNICAL SUPPORT

For assistance and manual updates, contact Technical Support at the 
following locations:

North America   

    Europe

(317) 916-4274   

 

     (+) 353-21-4321-266

www.hornerautomation.com        www.hornerautomation.eu
[email protected]

 

     

[email protected]

page 2 of 2

 INSTALLATION 

The HE959CNX116 is compact and mounts on DIN-rail. Each 
I/O module installed adds width in increments of 19mm. 

NOTE

The distance between wiring duct and surrounding modules 
should be at least 50mm apart.

Modules can be added after the HE959CNX116 base has been 
installed on the DIN-rail and can be hot swapped with power 
applied.  I/O scanning will stop until the correct modules for 
the system are detected in all slots.

I/O modules are physically added with the following procedure:

1. 

Connect the bus connectors together to form a backplane 
that can accept up to 8 modules including the CNX116 or 
another base.

2.  Snap the bus connectors into the DIN rail.  The DIN rail 

should be 35 mm × 7.5 mm and made to EN 60715 stan-
dards.

3.  Place the CNX116 or other bus head to the leftmost con-

nector.

4.  Inset modules buy latching at the top oof the DIN rail first 

and rocking down until the latch at the bottom of the DIN 
rail engages.

5.  To remove a module, insert a flat blade screwdriver into 

the metal DIN rail latch at the bottom of the module.  Pry 
down to the release the latch, the rock the module up and 
off the DIN Rail. Modules may be removed while powered 
however I/O scanning on the remaining modules will stop 
and I/O will go to the default state until a new module is 
inserted and all modules in the configuration are present.

Summary of Contents for HE959CNX116

Page 1: ...es 0 10V 0 20mA 4 20mA 0 60mV 0 10V 0 20mA 4 20mA 0 60mV 16 Bit AI Full Scale 0 20 Thermocouple J K T N E R S B Converter Type 16 Bit ADC RTD PT100 PT1000 RTD Excitation Current 250mA 1 4 Digital Outputs Inputs per Module 2 Commons per Module 1 Output Type Sourcing with 10kΩ pull down Absolute Max Voltage 28VDC Output Protection Short Circuit Max Output per Point 2A Max Total Out Current 4A Max Ou...

Page 2: ...ld be followed in the installation of this product b Shielded twisted pair wiring should be used for best performance c Shields should be grounded at one end only preferably at the end providing the best noise shunting SAFETY PART NUMBER HE959CNX116 TECHNICAL SUPPORT For assistance and manual updates contact Technical Support at the following locations North America Europe 317 916 4274 353 21 4321...

Page 3: ...uts Digital Analog Number of Channels 2 Digital or Analog Configured as Analog I O Analog Input Ranges 4 20mA 0 10V Analog Input Data Ranges 0 4000 2000 2000 0 1000 0 32000 Alarm Value Register Configured to Digital Inputs Digital Input Ranges 24V 12V 5V Custom Input Voltage Range 0 24VDC Absolute Max Voltage 30VDC Input Impedance 10kΩ Custom Digital Input Ranges Threshold ON Threshold OFF OFF to ...

Page 4: ...only usually at the DC supply powering the network The network DC supply should have its V terminal connected directly to earth ground If multiple DC supplies are used to power the network the V from any one supply should be connected only to nodes it is powering disconnected from other sections powered by other supplies The V connection should be continuous across the entire network although V sh...

Page 5: ...Q 0 10V Analog Out 10VDC 4 20 mA Analog Out OV AQ 20mA Digital Analog In 24V 12V 5V Custom Current Mode I1 0V 20mA Digital Out Positive Logic vs Negative Logic Wiring The OCS can be wired for positive or negative logic inputs 0V I1 0V I1 Positive Logic In Negative Logic In 0 10VDC Voltage Mode I1 0V Universal Analog Input 1a 1b 1c 0 10VDC NC 0 10V Analog In 1c 1a 1b 60mV 60mV mV In NC Thermocouple...

Page 6: ...D of each base Status Register Location where fifteen consecutive words are reported Digital Inputs Digital Outputs Analog Inputs Analog Outputs Start starting locations for each type of I O for this base Be careful to choose starting addresses that do not conflict with OCS built in I O mapping Comm Timeout Maximum amount of time the HE959CNX116 will wait to act on a communications timeout 40 to 2...

Page 7: ...guration mismatch error of each IO Modules Module 1 to Module 8 IOE Each bit bit9 bit 16 represents IO modules error Module 1 to Module 8 WDG TRIP IO base watchdog trip count IOCS Each bit bit9 bit 16 represents IO modules calibration status Module 1 to Module 8 PUP Power up error sticky bit OFFLINE OCSIO is offline DI1 US High when Digital input 1 is in undefined state DI2 US High when Digital in...

Page 8: ... ON Flash 1Hz OCS Run Mode ON ANY ANY ANY Onboard I O Fault ON OFF ON ON Invalid Dynamic Configuration ON Flash 1Hz ON ON Power Up Waiting to be Configured ON ON Flash 1Hz Flash 1Hz LED Indicators for Individual I O Channels I1 Digital Input 1 active I2 Digital Input 2 active Q1 Digital Output 1 active Q2 Digital Output 2 active AI1 Analog Input Active AQ1 Analog output Active NOTE Channel LED wil...