3 Configuration
Procedure
1.
Interfacing the PCU via the Master Control (OCS in this example)
NOTE: The Network Baud Rate of the PCU unit is set to 125K.
The controller portion of OCS products is programmed in ladder logic via the Windows-based Cscape
(Control Station Central Application Programming Environment) package.
a.
Run Cscape and establish a connection to the Master OCS. The default screen appears.
b.
At the top of the menu bar, click on the
Program
tab.
c.
Select
Network Config
from the pull-down menu.
d.
Click the
Option
tab. The following
Network Configuration
screen appears:
Figure 2 – Network Configuration Screen
e.
Click the
Network Required
box to the other network options.
f.
Click the
Network Optimized
box to speed network transfers.
g.
Fill in the
Number of Network IDs required by the Master OCS
. (Minimum number is 4 to support
one PCU). Enter 17 or more in the
Max Packets per Scan
box to enable all packets to be transferred
each scan (1 – 32 packets).
h.
Press
OK
.