WIRING 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

INSTALLATION AND SAFETY 

 
Special care must be taken with grounded junction sensors to avoid applying a voltage potential to the 
thermocouple junction. 
 
Extension wire of the proper Thermocouple type must be used.  Keep total wire resistance less than 
100

 to maintain rated accuracy. 

 
Route extension wiring in its own conduit.  Shielded, twisted pair extension wiring offers best noise 
immunity. 
 
If shielded wiring is used, a good earth ground connection is critical.   
 
Recommended wire size for terminal strip is 24 AWG. 
 
Adhere to the following safety precautions whenever any type of connection is made to the module. 
 
Connect the green safety (earth) ground first before making any other connections.  
 
When connecting to electric circuits or pulse-initiating equipment, open their related breakers.  Do not 
make connections to live power lines.    
 
Make connections to the module first; then connect to the circuit to be monitored.   
 

Summary of Contents for HE693THM166

Page 1: ... temperature values may be reported to the PLC AI I O table in 0 5 C or 0 5 F increments This module features open circuit detection where the AI register goes to its maximum value upon an open circuit condition and a corresponding I bit is energized Field wiring is connected to a special high density 32 position removable terminal block Recommended wire size is 24 AWG Figure 1 HE693THM166 Front V...

Page 2: ...ode Rejection 100dB A D Conversion Type Integrating Input Range Temp X 210 to 1200 C 2 C Maximum Reading not guaranteed below 200 C N 270 to 1300 C R 0 to 1768 C C 0 to 2320 C A D Conversion Time 40 channels per second Resolution 0 5 C or 0 5 F Operating Temperature 0 to 60 C 32 to 140 F Accuracy 0 5 C typical J K N T Relative Humidity 5 to 95 non condensing NOTE Model F and later support the Exte...

Page 3: ...ets the thermocouple type The effect of digital filtering set with Byte 2 on module response to a temperature change temp change completed vs time Table 3 Temperature Scaling Byte 3 Formula 0 C AI 2 1 F AI 2 Temperature values are written to the AI registers in 0 5 C or 0 5 F increments depending upon the value of Byte 3 0 10 20 30 40 50 60 70 80 90 100 0 2000 4000 6000 8000 Temperature Change Com...

Page 4: ... twisted pair extension wiring offers best noise immunity If shielded wiring is used a good earth ground connection is critical Recommended wire size for terminal strip is 24 AWG Adhere to the following safety precautions whenever any type of connection is made to the module Connect the green safety earth ground first before making any other connections When connecting to electric circuits or puls...

Page 5: ...aking any connection to a power line Make sure the unit is turned OFF before making connection to terminals Make sure all circuits are de energized before making connections Before each use inspect all cables for breaks or cracks in the insulation Replace immediately if defective 6 TECHNICAL ASSISTANCE For manual updates and assistance contact Technical Support at the following locations North Ame...

Page 6: ...PAGE 6 06 December 2004 MAN0090 05 NOTES ...

Reviews: