Restore OCS Data:
When initiated, this will allow the user to manually copy the backed-up data from the onboard
Flash to the Battery-Backed RAM.
A restore operation will be automatically initiated if a backup has been previously created and
on power-up the Battery-Backed RAM registers fail their check.
The following process is implemented to restore data:
•
The controller will be placed in IDLE mode.
•
Data will be copied from onboard Flash to OCS Battery-Backed RAM
•
The controller will reset.
•
The controller will be put in RUN mode if the AutoRun setting is ‘Yes’ else it will remain
in IDLE mode.
XLE:
XLT:
Figure 16.4
–
Restore OCS Data
%SR164.3 is set to 1 only when an automatic restore operation is performed - not on a manual
one. This bit is reset to the value of 0 when a new backup is created.
Restoring of data can be manually performed by selecting RESTORE option from the Backup /