Maintenance
Batteries_Rail_Power_Manual_en02.docx
39
Note
Note
The pole screws M8 with plastic head must be replaced by new ones because the screw
connection is secured with a micro-encapsulated adhesive.
For connections with M8 pole screws without plastic head, you can reuse the screws, but must
use new spring washers.
Torque: 20 Nm
Result: The defect connector was exchanged.
9.2.3.
Exchange of the temperature sensor
Target: The defect temperature sensor is exchanged.
1. Disconnect the Cannon plug.
2. Remove the defective temperature sensor.
3. Install the new temperature sensor.
4. Reconnect the Cannon plug.
5. Check the charging voltage, see
9.1.2 Measurement of the charging voltage on page 31.
Result: The defect temperature sensor was exchanged.
Terminal screw M8 with plastic head;
Wrench opening 22 mm
Terminal screw M8
Spring washer
Pole shoe
Connector
Temperature sensor